当前位置:文档之家› QGDW_559-2010 输电线路杆塔倾斜监测装置技术规范

QGDW_559-2010 输电线路杆塔倾斜监测装置技术规范

II
2009Q / GDW 559 — 2010
输电线路杆塔倾斜监测装置技术规范
1 范围
本标准规定了架空输电线路杆塔倾斜监测装置的功能要求、技术要求、试验项目、试验方法、安装、 调试、验收等。
本标准适用于交流 66kV~1000kV、直流±400kV~±800kV 架空输电线路。
2 规范性引用文件
本标准的附录 A 为规范性附录。 本标准由国家电网公司生产技术部提出并解释。 本标准由国家电网公司科技部归口。 本标准主要起草单位:中国电力科学研究院。 本标准参加起草单位:华北电网有限公司、山西省电力公司、河南省电力公司、重庆市电力公司。 本标准主要起草人:于钦刚、李红云、郭志广、李红旗、刘亚新、周国华、李峻峰、罗永勤、郑凯、 倪康婷、张帆、裴冠荣。
5.2 数据处理与判别 a) 具备数据合理性检查分析功能,对采集数据进行预处理,自动识别并剔除干扰数据; b) 具备对原始采集量的一次计算功能,得出直观的杆塔倾斜状态量数据。
5.3 数据存储 应能循环存储至少 30 天的杆塔横向、纵向角度与倾斜度状态量数据。
5.4 数据输出 输出的信息包括:杆塔横向、纵向角度与倾斜度状态量数据,及电源电压、工作温度、心跳包等工
ICS 29.240ICS ××× P ××× 备案号:×××
2009Q / GDW 559 — 2010
Q/GDW
国家电网公司企业标准
Q / GDW 559 — 2010
输电线路杆塔倾斜监测装置技术规范
Technical specification for tower inclination monitoring device on overhead transmission lines
4 监测内容及装置组成
4.1 监测内容 倾斜度、顺线倾斜度、横向倾斜度、顺线倾斜角、横向倾斜角。
4.2 装置组成 一般由一体化杆塔倾斜监测装置组成。
5 功能要求
5.1 数据采集要求 a) 能传感、采集杆塔纵向和横向倾斜角度,进行相应存储,并将测量结果通过通信网络传输到状 态监测代理或状态监测主站; b) 具备自动采集功能,按设定时间间隔自动采集杆塔横向与纵向倾斜角度,最小采集间隔宜大于 30 分钟,最小采集间隔应不大于 24 小时,默认时间间隔为 60 分钟;在监测到超过设定阀值 时,具备加密采集的功能; c) 具备受控采集功能,能响应远程指令,按设置采集方式、自动采集时间、采集时间间隔、采集 点数启动采集; d) 宜具备电源电压采集功能。
作状态数据,数据输出要求符合附录 A。 5.5 通信功能
2
2009Q / GDW 559 — 2010
通信接口和应用层数据传输规约应满足“Q/GDW 242-2010 输电线路状态监测装置通用技术规范” 相关要求。 5.6 硬件与软件
a) 具备对装置自身工作状态包括采集、存储、处理、通信等的管理与自检测功能; b) 当判断装置出现运行故障时,能启动相应措施恢复装置的正常运行状态。 5.7 远程更新、配置与调试 a) 应具备身份认证、远程更新程序的功能,具备完善的更新机制与方式; b) 应具备按远程指令修改采集频率、采样时间间隔、网络适配器地址等参数的功能; c) 应具备动态响应远程时间查询/设置、数据请求、复位等指令的功能; d) 宜能按远程指令进入远程调试模式,并输出相关调试信息。 5.8 其他功能 为了保证测量的准确性,杆塔倾斜监测装置初装时应该具备垂直度、水平度调节功能。
1
Q / GDW 559 — 2010
3 术语和定义
“Q/GDW 242-2010 输电线路状态监测装置通用技术规范”确立的以及下列术语和定义适用于本标 准。 3. 1
杆塔倾斜监测装置 tower inclination monitoring device 满足测量数字化、输出标准化、通信网络化特征,具备自检、自恢复功能,对架空输电线路杆塔的 倾斜度进行在线监测的一种监测装置,并通过信道将数据传送到状态监测代理装置或状态监测主站。 3. 2 倾斜度 inclination 杆塔偏离中心线的倾斜值与监测点地面高度之比,也称为综合倾斜度。 3. 3 顺线倾斜度 fair line inclination 杆塔沿线路方向的倾斜值与监测点地面高度之比。 3. 4 横向倾斜度 orientation inclination 杆塔在垂直于线路方向的倾斜值与监测点地面高度之比。
6.4 主要技术参数 6.4. 1 监测范围
杆塔倾斜角动态测量范围:双轴±10°。 6.4. 2 准确度
杆塔倾斜角测量误差:≤± 0.05°。 6.5 基本技术要求
a) 应有防雨、防潮、防尘、防腐蚀措施; b) 外壳的防护性能应符合 GB 4208 规定的 IP65 级要求; c) 杆塔倾斜监测装置的结构不应对杆塔产生磨损或其他机械伤害; d) 杆塔倾斜监测装置应采取防盗、防振、防松措施,保证在运行中不松脱,而且不降低杆塔的机
2010-12-27 发布
2010-12-27 实施
国家电网公司 发 布
2009Q / GDW 559 — 2010
目次
前言 ··································································································································································· II 1 范围 ····························································································································································· 1 2 规范性引用文件·········································································································································· 1 3 术语和定义·················································································································································· 2 4 监测内容及装置组成 ·································································································································· 2 5 功能要求······················································································································································ 2 6 技术要求······················································································································································ 3 7 试验项目及方法·········································································································································· 4 8 安装、调试与验收 ······································································································································ 5 附录 A(规范性附录) 杆塔倾斜监测装置数据输出接口·········································································· 7 编制说明 ··························································································································································· 9
6 技术要求
6.1 使用环境条件 a) 环境温度:-25℃~+45℃(普通型)或-40℃~+45℃(低温型); b) 相对湿度:5%RH~100%RH; c) 大气压力:550hPa~1060hPa。
6.2 工作温度 -25℃~+70℃(工业级)或-40℃~+85℃(扩展工业级)。
6.3 外观及标记 a) 外观应整洁完好,无明显划痕; b) 监测装置上应有型号、名称、出厂编号、出厂日期、制造厂名等ห้องสมุดไป่ตู้记。
I
Q / GDW 559 — 2010
前言
输电线路状态监测系统是智能电网建设输电环节的重要组成部分,是实现输电线路状态运行检修管 理,提升生产运行管理精益化水平的重要技术手段。为科学规范地建设坚强智能电网输电线路状态监测 系统,确保输电线路状态监测系统技术标准和平台统一,装置数据有效、稳定可靠、先进适用,特制定 本标准。
下列文件对于本文件的应用是必不可少的。凡是注日期的引用文件,仅注日期的版本适用于本文件。 凡是不注日期的引用文件,其最新版本(包括所有的修改单)适用于本文件。
相关主题