※ (1) : caution when using Function Code 0x05(WRITE)1). RESET : 0xFF00, Use only TRIP state2). CLEAR RESET : 0xFF00, THERMAL MEMORY CLEAR RESET ※2 : Trip CAUSE0x0000 TRIP_NON0x0001 TRIP_DEFINITE0x0002 TRIP_INVERSE0x0004 TRIP_LOCK0x0008 TRIP_STALL0x0010 TRIP_INSTANT0x0020 TRIP_UNDERCURR0x0040 TRIP_UNBALANCE0x0080 TRIP_PHASEFAIL0x0100 TRIP_REVERSEPHASE0x0200 TRIP_GROUND_ZCT0x0400 TRIP_GROUND_NCT※3 : 3-PHASE Current, Earth Fault Current(NCT), TRIP 3-phase Current. (TRIP) Current : Ir, Is, It. Read data : 500 => 0.50A, 1200 => 1.20A,,, 6563 => 6.56A,,,,, 10000 => 10.00A(TRIP) Current = Read data / 1000. Earth fault current (NCT). Read data : 500 => 500mA(0.5A), 1200 => 1200mA(1.2A), 2345 => 2345mA(2.345A)Earth fault current(NCT) unit is mA.# In case DOUBLE WORDS(FLOAT) DATA, Response Data Format is swaped by setting IMP GROUP B's c.S-P : ON or OFF ex) c.S-P : ON => SWAP is appliedOriginal Data : 0x12345678 ==> Response Data Value : 0x5678, Response Data Value : 0x1234c.S-P : OFF => SWAP is not appliedOriginal Data : 0x12345678 ==> Response Data Value : 0x1234, Response Data Value : 0x5678※4 : Earth Fault Current(ZCT), Trip Earth Fault Current(ZCT). Read data : 30,000 => 0.030A, 50,000 => 0.050A,,, 1,000,000 => 1.000A,,,,, 3,000,000 => 3.00A(TRIP) Current = Read data / 1,000,000Earth fault current(ZCT) unit is uA.# In case DOUBLE WORDS(FLOAT) DATA, Response Data Format is swaped by setting IMP GROUP B's c.S-P : ON or OFF ex) c.S-P : ON => SWAP is appliedOriginal Data : 0x12345678 ==> Response Data Value : 0x5678, Response Data Value : 0x1234c.S-P : OFF => SWAP is not appliedOriginal Data : 0x12345678 ==> Response Data Value : 0x1234, Response Data Value : 0x5678※5 : Run TimeIn case Run time(hour) : 1201, Run time(minute) : 101201 / 24 = 50.01 => 50 days 1 hour 10 minutes※6 : Rating current setting. Data range. In case 10A tyep, Data range is 5~100 (5 : 0.5A, 10 : 1A, 100 : 10A). In case 100A tyep, Data range is 50~1000(50 : 5A, 100 : 10A, 1000 : 100A). CT ratio is not applied.※7 : CT Ratio. Data range : 0 ~ 201. Datas mean 0 => 0.25, 1 => 0.5, 2 => 1, 3 => 2,,,,,,,,,,,,,, 201 => 200※8 : Earth Fault current(ZCT). Data ragne : 0 ~ 3000. Data means 0=>OFF, 30=>30mA(0.03A), 50=>50mA(0.05A), 100=>100mA(0.1A), 1000=>1000mA(1A), 3000=>3000mA(3A) ※9 : Earth fault operating time. Data range : 5 ~ 100. Data means 5 => 50ms(0.05S), 10 => 100ms(0.1S),,,,,,,,,, 100 => 1000ms(1.0S)※10 Caution when using Function Code 0x06,0x10(WRITE)# Run time set. Data range : 0 ~ 8760, 1 step. 0 : OFF :: OrH function do not work.# LOCK protection. Data range : 0(OFF),200,300,400,500,600,700,800 (In case 0x10, 0(OFF),2,3,4,5,6,7,8) ). Out of data occurs error.# STALL protection. Data range : 0(OFF),150,200,250,300,350,400,450,500 (In case 0x10, 0(OFF),15,20,25,30,35,40,45,50) ) . Out of data occurs error.# Instantaneous protection. Data range : 0(OFF),500,600,700,800,900,1000 (In case 0x10인 경우 0(OFF),5,6,7,8,9,10) ). Out of data occurs error.※11 Caution when reading TRIP CausesNumber 1 Fault info. is a last Fault.Fault info. Is read one by one.EX) From Number 1 fault time to number 1 earth fault current data is available.From Number 1 fault R pahse current to number 1 fault T phase current data is available.From Number 1 fault R pahse current to number 2 fault T phase current data is not available※12 Relay output info.※13 In case 0x10 FUNCTION, bit mapping.※14 In case 0x10 FUNCTION, bit mapping.※15 : In case 0x10 FUNCTION , Ratind current setting. Settind data range is 5~100.- In case 10A tyep : 5~100 (5 : 0.5A, 10 : 1A, 100 : 10A). CT ratio is not applied.※16 : In case 0x10 FUNCTION, LOCK or Instantaneous setting. writing value = setting value / 100EX) if 500%, writing value is 5, if 1000%, writing value is 10.※17 : In case 0x10 FUNCTION, STALL setting. writing value = setting value / 10※20 : Fault Phase info. (Phase loss, Phase unbalance, Earth fault(ZCT,NCT)). Data range : 0 ~ 32. Read value : 0 => OFF, 1 => 0.03A, 2 => 0.05A, 3 => 0.1A,,,,,,,,,,,,,, 32 => 3.0A。