当前位置:文档之家› 短路容量计算

短路容量计算

新富煤矿井上下各变电所短路容量计算2012年3月目录1.一井短路容量计算: (2)2.二井短路容量计算: (5)3.三井短路容量计算: (8)4.五井短路容量计算: (11)5.六井短路容量计算: (14)6.七井短路容量计算: (17)7.八井短路容量计算: (19)8.九井短路容量计算: (22)9.十四井短路容量计算: (25)10.十六井短路容量计算: (28)1.一井短路容量计算:已知新富变变电所 6.3KV 母线最大及最小运行方式短路容量分别为Sd=153MVA 、Sd=105.84MVA ,线路2216电源电缆型号为LGJ-3*70长度为1019米,每公里电阻为0.516Ω,每公里电抗为0.061Ω,GJ-3*50长度为697米,每公里电阻为0.65Ω,每公里电抗为0Ω;(1)线路2216最大运行方式短路容量计算: 电源短路容量S d =118MVA电源系统电抗:X s =U p 2/S s =6.32/153=0.3364Ω)电缆电阻:R g = ∑( RiLi / 1000 )=0.516×1019/1000+ 0.65×697/1000=0.967(Ω)电缆电抗:X g = ∑(XiLi / 1000)=0.061×1019/1000 =0.062(Ω)总 电 阻:()22gsg XXR Z++=()22062.03364.09788.0++==1.046(Ω)三相短路电流()A Z U I P d 3477046.13630033=⨯==两相短路电流()()AI I dd 30113477866.02332=⨯==短路容量:S d =3⨯()3d I ⨯U P ⨯10-6=3⨯3477⨯6300⨯10-6=37.94MVA(2)线路2216最小运行方式短路容量计算: 电源短路容量S d =75MVA电源系统电抗:X s =U p 2/S s =6.32/105.84=0.5292(Ω)电缆电阻:R g = ∑( RiLi / 1000 )=0.516×1019/1000+ 0.65×697/1000=0.9788(Ω)电缆电抗:X g = ∑(XiLi / 1000)=0.061×1019/1000 =0.062(Ω)总 电 阻:()22gsg XXR Z++=()22062.05292.09788.0++==1.13(Ω)三相短路电流()AZ U I P d 320813.13630033=⨯==两相短路电流()()A I I dd 27783208866.02332=⨯==短路容量:S d =3⨯()3d I ⨯U P ⨯10-6=3⨯3208⨯6300⨯10-6=35.01MVA已知新富变变电所 6.3KV 母线最大及最小运行方式短路容量分别为Sd=118MVA 、Sd=75MVA ,线路2113电源电缆型号为LGJ-3*70长度为689米,每公里电阻为0.516Ω,每公里电抗为0.061Ω,GJ-3*50长度为1200米,每公里电阻为0.65Ω,每公里电抗为0Ω;(1)线路2113最大运行方式短路容量计算: 电源短路容量S d =118MVA电源系统电抗:X s =U p 2/S s =6.32/153=0.3364Ω)电缆电阻:R g = ∑( RiLi / 1000 )=0.516×689/1000+ 0.65×1200/1000=1.14(Ω)电缆电抗:X g = ∑(XiLi / 1000)=0.061×689/1000 =0.04(Ω)总 电 阻:()22gsg XXR Z++=()2204.03364.014.1++==1.20(Ω)三相短路电流()A ZU I P d 303920.13630033=⨯==两相短路电流()()AI I dd 26323039866.02332=⨯==短路容量:S d =3⨯()3d I ⨯U P ⨯10-6 =3⨯3039⨯6300⨯10-6=33.16MVA(2)线路2113最小运行方式短路容量计算: 电源短路容量S d =75MVA电源系统电抗:X s =U p 2/S s =6.32/105.84=0.5292(Ω)电缆电阻:R g = ∑( RiLi / 1000 )=0.516×689/1000+ 0.65×1200/1000=1.14(Ω)电缆电抗:X g = ∑(XiLi / 1000)=0.061×689/1000 =0.04(Ω)总 电 阻:()22gsg XXR Z++=()2204.05292.014.1++==1.27(Ω)三相短路电流()A Z U I P d 286113.13630033=⨯==两相短路电流()()A I I dd 24783208866.02332=⨯==短路容量:S d =3⨯()3d I ⨯U P ⨯10-6=3⨯2861⨯6300⨯10-6=31.44MVA2.二井短路容量计算:已知供电部变电所 6.3KV 母线最大及最小运行方式短路容量分别为Sd=118MVA 、Sd=75MVA ,线路11205电源电缆型号为LGJ-3*70长度为2130米,每公里电阻为0.516Ω,每公里电抗为0.061Ω,高压电缆MYJV-3*35长度为620米每公里电阻为0.610Ω,每公里电抗为0.0637Ω;线路11204电源电缆型号为LGJ-3*70长度为1870米,每公里电阻为0.516Ω,每公里电抗为0.061Ω,高压电缆MYJV-3*35长度为620米,每公里电阻为0.610Ω,每公里电抗为0.0637Ω线路,11204最大运行方式短路容量计算: 电源短路容量S d =118MVA电源系统电抗:X s =U p 2/S s =6.32/118=0.3364Ω)电缆电阻:R g = ∑( RiLi / 1000 )=0.516×2130/1000+0.0637×620/1000=1.48(Ω)电缆电抗:X g = ∑(XiLi / 1000)=0.061×1019/1000+0.0637×620/1000 =0.17(Ω)总 电 阻:()22gsg XXR Z++=()2217.03364.048.1++==1.56(Ω)三相短路电流()AZ U I P d 232956.13630033=⨯==两相短路电流()()A I I dd 20172329866.02332=⨯==短路容量:S d =3⨯()3d I ⨯U P ⨯10-6 =3⨯2329⨯6300⨯10-6=25.42MVA(2)线路11205最小运行方式短路容量计算: 电源短路容量S d =75MVA电源系统电抗:X s =U p 2/S s =6.32/75=0.5292Ω)电缆电阻:R g = ∑( RiLi / 1000 )=0.516×2130/1000+0.0637×620/1000=1.48(Ω)电缆电抗:X g = ∑(XiLi / 1000)=0.061×1019/1000+0.0637×620/1000 =0.17(Ω)总 电 阻:()22gsg XXR Z++=()2217.05292.048.1++==1.63(Ω)三相短路电流()A Z U I P d 222663.13630033=⨯==两相短路电流()()A I I dd 19272226866.02332=⨯==短路容量:S d =3⨯()3d I ⨯U P ⨯10-6=3⨯2226⨯6300⨯10-6=24.32MVA(3)线路11204最大运行方式短路容量计算: 电源短路容量S d =118MVA电源系统电抗:X s =U p 2/S s =6.32/118=0.3364Ω)电缆电阻:R g = ∑( RiLi / 1000 )=0.516×1870/1000+0.0637×620/1000=1.34(Ω)电缆电抗:X g = ∑(XiLi / 1000)=0.061×1870/1000+0.0637×620/1000 =0.15(Ω)总 电 阻:()22gsg XXR Z++=()2215.03364.034.1++==1.43(Ω)三相短路电流()A Z U I P d 254443.13630033=⨯==两相短路电流()()AI I dd 22032544866.02332=⨯==短路容量:S d =3⨯()3d I ⨯U P ⨯10-6=3⨯2544⨯6300⨯10-6=27.76MVA(4)线路11204最小运行方式短路容量计算: 电源短路容量S d =75MVA电源系统电抗:X s =U p 2/S s =6.32/75=0.5292Ω)电缆电阻:R g = ∑( RiLi / 1000 )=0.516×1870/1000+0.0637×620/1000=1.34(Ω)电缆电抗:X g = ∑(XiLi / 1000)=0.061×1870/1000+0.0637×620/1000 =0.15(Ω)总 电 阻:()22gsg XXR Z++=()2215.05292.034.1++==1.51(Ω)三相短路电流()AZ U I P d 241451.13630033=⨯==两相短路电流()()AI I dd 20902414866.02332=⨯==短路容量:S d =3⨯()3d I ⨯U P ⨯10-6 =3⨯2414⨯6300⨯10-6=26.34MVA3.三井短路容量计算:已知新富变变电所 6.3KV 母线最大及最小运行方式短路容量分别为Sd=153MVA 、Sd=105.84MVA ,线路2216电源电缆型号为LGJ-3*70长度为1019米,每公里电阻为0.516Ω,每公里电抗为0.061Ω,GJ-3*50长度为2197米,每公里电阻为0.65Ω,每公里电抗为0Ω;高压电缆MYJV-3*35长度为600米每公里电阻为0.610Ω,每公里电抗为0.0637Ω;线路21414电源电缆型号为LGJ-3*120长度为2626米,每公里电阻为0.255Ω,每公里电抗为0.347Ω,高压电缆MYJV-3*35长度为600米每公里电阻为0.610Ω,每公里电抗为0.0637Ω2.4线路2216最大运行方式短路容量计算:电源短路容量S d =118MVA电源系统电抗:X s =U p 2/S s =6.32/118=0.3364(Ω)电缆电阻:R g = ∑( RiLi / 1000 )=0.516×1019/1000+ 0×2197/1000+0.0637×600/1000=2.3198(Ω)电缆电抗:X g = ∑(XiLi / 1000)=0.061×1019/1000+0.0637×600/1000 =0.1(Ω)总 电 阻:()22gsg XXR Z++=()221.03364.03198.2++==2.36(Ω)三相短路电流()AZ U I P d 154136.23630033=⨯==两相短路电流()()AI I dd 133********.02332=⨯==短路容量:S d =3⨯()3d I ⨯U P ⨯10-6=3⨯1541⨯6300⨯10-6=16.81MVA(2)线路2216最小运行方式短路容量计算: 电源短路容量S d =75MVA电源系统电抗:X s =U p 2/S s =6.32/75=0.5292(Ω)电缆电阻:R g = ∑( RiLi / 1000 )=0.516×1019/1000+ 0.65×2197/1000+0.0637×600/1000=2.3198(Ω)电缆电抗:X g = ∑(XiLi / 1000)=0.061×1019/1000+0.0637×600/1000 =0.1(Ω)总 电 阻:()22gsg XXR Z++=()221.05292.03198.2++==2.4(Ω)三相短路电流()A Z U I P d 15134.23630033=⨯==两相短路电流()()A I I dd 131********.02332=⨯==短路容量:S d =3⨯()3d I ⨯U P ⨯10-6 =3⨯1513⨯6300⨯10-6=16.51MVA(3)线路21414最大运行方式短路容量计算: 电源短路容量S d =118MVA电源系统电抗:X s =U p 2/S s =6.32/118=0.3364Ω)电缆电阻:R g = ∑( RiLi / 1000 )=0.255×2626/1000+0.0637×600/1000=1.035(Ω)电缆电抗:X g = ∑(XiLi / 1000)=0.347×1019/1000+0.0637×600/1000 =0.9494(Ω)总 电 阻:()22gsg XXR Z++=()229494.03364.0035.1++==1.65 (Ω)三相短路电流()A Z U I P d 220365.13630033=⨯==两相短路电流()()A I I dd 19082203866.02332=⨯==短路容量:S d =3⨯()3d I ⨯U P ⨯10-6 =3⨯2203⨯6300⨯10-6=24.04MVA(4)线路21414最小运行方式短路容量计算:电源短路容量S d =75MVA电源系统电抗:X s =U p 2/S s =6.32/75=0.5292(Ω)电缆电阻:R g = ∑( RiLi / 1000 )=0.255×2626/1000+0.0637×600/1000=1.035(Ω)电缆电抗:X g = ∑(XiLi / 1000)=0.347×1019/1000+0.0637×600/1000 =0.9494(Ω)总 电 阻:()22gsg XXR Z++=()229494.05292.0035.1++==1.80(Ω)三相短路电流()AZ U I P d 201480.13630033=⨯==两相短路电流()()AI I dd 17452014866.02332=⨯==短路容量:S d =3⨯()3d I ⨯U P ⨯10-6=3⨯2014⨯6300⨯10-6=2199MVA4.五井短路容量计算:1、五井富强变电所95105、91212线路最大及最小运行方式短路容量计算: 已知富强变6.3KV 母线最大运行方式短路容量Sd=153MVA ,最小运行方式短路容量为Sd=105.84,线路95105、91212线路型号均为LGJ-50mm 2长度分别为10940米和15040米,每公里电阻为0.65Ω,每公里电抗为0Ω。

相关主题