“Configuration Menu”
SELECT:
ATO/ATC (AIR ACTION) LINEAR/ EQUAL 30%/ EQUAL 50%/ QUICK/ CUSTOM TS ON/OFF (Tight Shut-Off) (Use +/- To Set Value) ENGLISH/FRENCH (LCD Display Language)
SETUP Æ
DISPLAY ERROR MESSAGES:
NOERR:
No Error
RESET:
Reset occurred
LOW POWER:
Input current < 3.6 mA
ACT ERR:
Unable to position valve
AIR LOW:
Supply pressure < 10 psi
TUNE (Auto-Tune) (Self Calibration)
TUNE (Allow the required time for self Tuning) Sub-Routine will display sequence of Steps from 1 to 3, task in complete when LCD Reads “TUNE”. Ç SETUP (Setup Menu) È CALIB (Calibration Menu) Ç MANUAL (Return to Manual menu ) È SETUP (Setup Menu) Ç NORMAL (Normal Operating Mode Menu) This selection returns the SVI-II into “Normal Operating Mode” LCD will Display Valve Position and Control Signal Stroke the valve with 4-20 mA Loop Calibrator to confirm Performance.
“Manual Mode Menu”
MAN POS (Manual Positioning) SETUP Æ NORMAL Æ
VIEW DATA DISPLAY CONFIG SETTINGS SINGLE/DOUBLE ATO/ATC LINEAR/ EQ30%/ EQ50%/ QO/ CUSTOM TS ON/OFF SIG LOW (Typical 4mA) SIG HIGH (Typical 20mA
POS ERR:
Position Deviation Alarm (T 1)
POS FAULT:
Positioner failed (Failsafe)
CALIB ERR:
Calibrate failed
STOP ERR:
Find Stops failed
TUNE ERR:
Auto Tune failed
ATO (* TO ATC) CONFIGURE VALVE ACCORDINGLY, AIR TO OPEN (ATO) OR AIR TO CLOSE (ATC) LINEAR (* TO EQUAL 50) CONFIGURE VALVE ACCORDINGLY, LINEAR / EQUAL PERCENTAGE 50 CONTROL Ç SETUP (Setup Menu) È CONFIG (Configuration Menu) È CAL IB (Calibration Menu)
TEMP ERR:
Temperature detects > 80 C or < -40 C
NUM ERR_R:
FRAM record error
RAM ERR:
RAM data bad checksum
FLASH ERR:
Flash memory failed checksum
STACK ERR:
MANUAL (Position set by Command) Setup Mode (For Configuration & Calibration)
ALL MODES (Always accessible)
1250 Hall Court, Deer Park. Texas 77536 Tel. (281) 884-1000 Fax (281) 884-1010
STD DIAG:
Standard Diagnostics failed
EXT DIAG:
Extended Diagnostics failed
CMD STOP:
Hart Command aborted
BIAS ERR:
Position algorithm error
I/P LIMIT:
I/P current too high or too low
Masoneilan®
SVI-IIAP PUSH BUTTON SHORT CUTS
* Select or Toggles value (Enter Key) + Increase Value or Steps Forward - Decreases Value or Steps Backward
STOPS (Auto Stop Limits) (Find Zero & Span)
STOPS (THIS FUNCTION WILL IDENTIFY MECHANICAL RANGE OF THE VALVE ) (ALLOW SVI TIME TO DRIVE VALVE CLOSE & OPEN )
Any button to EXIT to “Normal Operating Mode”
Quick Set-up & Calibration
Operator Action
* Select
+ Next Option
* Select ++ Next Option * Select * Select
+ Next Option
SETUP Æ
The chart color code represents the control mode of the SVI –II in which the function is available:
NORMAL – OPERATE (Position Follows Control Signal (4-20 mA)
Masoneilan®
PUSH BUTTON GUIDE FOR SVI-IIAP
Firmware 3.11(2006)
Basic Diagnostics
* Select or Toggles value (Enter Key) + Increase Value or Steps Forward - Decreases Value or Steps Backward
Any button to EXIT to “Normal Operating Mode”
**NORMAL MODE ** Display Sequence Position Input Signal (mA)
MANUAL Æ VIEW DATA Æ VIEW ERR Æ CLR ERR Æ NORMAL Æ
CLEAR FAULTS “Wait”
“Manual Positioning”
Enter a ቤተ መጻሕፍቲ ባይዱew position value Use +/- To Change Use * To Exit Æ
“Setup Menu”
CONFIG Æ CALIB Æ MANUAL Æ VIER ERR Æ CLR ERR Æ
RAM stack overflow
FCTRYMODE: Factory mode failure (Failsafe)
POS SENSR:
Hall Effect sensor error
“Calibration Menu”
SELECT:
STOPS (Find Stop Limits) STOP OP (Open Stop Adjustment)(Use +/- To Set) TUNE (Auto-Tuning) SIG LOW (Low Signal, Typical Value 4ma) SIG HIGH (High Signal, Typical Value 20mA)
SVI-IIAP’s LCD Æ NORMAL (Normal Operating Mode Menu) È MANUAL (Manual Mode Menu) SIGNAL / POS—M (Manual Positioning) È SETUP (Setup Menu) È CONFIG (Configuration Menu)
1250 Hall Court, Deer Park. Texas 77536 Tel. (281) 884-1000 Fax (281) 884-1010
--Previous Options * Select + Next Option * Select * Select
++ Next Option * Select
--- Previous Option * Select + Next Option * Select + Next Option
* Select