当前位置:文档之家› 空调C7000通讯协议(世图兹 ASD531a)

空调C7000通讯协议(世图兹 ASD531a)

Stulz-Adr.

MODBUS-

adr.Description Beschreibung Modbus range mapped meaning

BMS-

access

Modbus-

function C7000IOC

C7000IOC

Chiller 00hardware type(controller type)Hardware-Typ(Steuerungs-Typ)0..13=C7000IOC;8=C7000AT;9=C700r3,(4)x x

88general error Allgemeiner Fehler0/1ok/error r1,(2)x x

12unit-type unit-type0..2551=CHP;12=FAU;13=CPP;14=Pr r3,(4)x x

36SW-version SW-Version0..655,35Version0..655,35Version r3,(4)x x

510Bus-ID Bus-ID0..310..31r3,(4)x x

612global adress Globale Adresse0..65535r3,(4)x x

Stulz-Adr.

MODBUS-

adr.Description Beschreibung Modbus range mapped meaning

BMS-

access

Modbus-

function C7000IOC

C7000IOC

Chiller 0

see combined list C7000common s.gemeinsame Liste C7000common

999

10001000PC-STOP(monitoring),BMS stop1PC-STOP(überwachung),BMS stop10/1maybe on/unit off rw1,(2),5x x 10011001REMOTE STOP(contact)FERN-STOP(Kontakt)0/1maybe on/unit off r1,(2)x x 10021002LOCAL STOP LOKAL-STOP0/1maybe on/unit off r1,(2)x x 10031003TIMER-STOP(weekly oper.)TIMER-STOP(w?chentlicher Betrieb)0/1maybe on/unit off r1,(2)x x 10041004SEQ.Stop(0=No,1=Yes)SEQ.Stop(0=Nein,1=Ja)0/1maybe on/unit off r1,(2)x x 10051005WARM UP STOP AUFW?RMEN STOP0/1maybe on/unit off r1,(2)x x 10061006Remote UPS FERN-UPS0/1inactive/active rw1,(2),5x x 10071007Local UPS Lokal-UPS0/1inactive/active r2,(1)x x 10081008G/CW-mode;G:1,CW:0G/CW-Modus;G:1,CW:00/1CW/G r1,(2)x

10091009manual operation manueller Betrieb0reset man.op./rw1,(2),5x x 10101010common alarm gemeinsamer Alarm0/1no alarm/alarm r2,(1)x x 10111011reset all alarms Alle Alarme zurückstellen0/1/reset rw1,(2),5x x 10121012manual operation raw output manueller Betrieb Roh-Output0/1inactive/active r1,(2)x x 10131013Unit on/off Einheit on/off0/1off/on r2,(1)x x 10141014maintenance necessary Wartung notwendig0/1no/yes r2,(1)x x 10221022unit temperature phys.unit Einheit Temperatur phys.Einheit0/1Celsius/Fahrenheit r1,(2)x x 10231023unit winter mode Einheit Winter-Modus0/1Summer/Winter r2,(1)x x 10241024day/night-mode Tag/Nacht-Modus0/1day/night r2,(1)x x 10251025CW2change-over CW2Umstellung0/1/force change over rw2,(1)x x 10261026CW2change-over state CW2Umstellungs-Status0/1/change over done r2,(1)x

10281028unit start by remote-on/off Start der Einheitüber Fernsteuerung on/off0/1inactive/active r2,(1)x x 10321032unit firmware-option1:OTE(automatic alarm Einheit firmware-Option1:OTE(automatische0/1r2,(1)x x 10331033unit firmware-option2:restart after fire alarm Einheit firmware-Option2:Neustart nach erle0/1r2,(1)x x 10341034unit firmware-option3:auto alarm reset for lim

Einheit firmware-Option3:Alarm-Selbstrücks0/1r2,(1)x x 10351035unit firmware-option4:special control of fans E inheit firmware-Option4:Spezialkontrolle vo0/1r2,(1)x x 10361036unit firmware-option5:special control of pump

Einheit firmware-Option5:Spezialkontrolle Pu0/1r2,(1)x x 10371037unit firmware-option6:special control Adaptiv Einheit firmware-Option6:Spezialkontrolle Ad0/1r2,(1)x x 14921492water inlet1,min temperature commonalarm Wassereinlass1,Min.-Temperatur gemeinsa0/1r1,(2)x 14931493water inlet1,max temperature commonalarm W assereinlass1,Max.-Temperatur gemeinsa0/1r1,(2)x 14941494water outlet1,min temperature commonalarm

Wasserauslass1,Min.-Temperatur gemeinsa0/1r1,(2)x 14951495water outlet1,max temperature commonalarm

Wasserauslass1,Max.-Temperatur gemeins0/1r1,(2)x 14961496water inlet2,min temperature commonalarm Wassereinlass2,Min.-Temperatur gemeinsa0/1r1,(2)x 14971497water inlet2,max temperature commonalarm W assereinlass2,Max.-Temperatur gemeinsa0/1r1,(2)x 14981498water outlet2,min temperature commonalarm

Wasserauslass2,Min.-Temperatur gemeinsa0/1r1,(2)x 14991499water outlet2,max temperature commonalarm

Wasserauslass2,Max.-Temperatur gemeins0/1r1,(2)x 15001500circuit1LP management common alarm conf LP Management gemeinsamer Alarm Konfigu0/1r1,(2)x x 15301530circuit1HP management common alarm con HP Management gemeinsamer Alarm konfig0/1r1,(2)x x 16001600circuit2LP management common alarm conf LP Management gemeinsamer Alarm Konfigu0/1r1,(2)x CC2 16301630circuit2HP management common alarm con HP Management gemeinsamer Alarm konfig0/1r1,(2)x CC2 17421742fire alarm common alarm config Feueralarm gemeinsamer Alarm konfig0/1r1,(2)x x 17431743water alarm common alarm config Wasseralarm gemeinsamer Alarm konfig0/1r1,(2)x x 17441744phase alarm common alarm config Phase Alarm gemeinsamer Alarm konfig0/1r1,(2)x x

Stulz-Adr.MODBUS-

adr.Description Beschreibung Modbus range mapped meaning

BMS-

access

Modbus-

function C7000IOC

C7000IOC

Chiller

17451745maintenance common alarm config Wartung gemeinsamer Alarm konfig0/1r1,(2)x x 17461746auto-restart after phase alarm Auto-Neustart nach Phase Alarm0/1inactive/active r2,(1)x x 17471747waterflow alarm common alarm config Wasserflussalarm gemeinsamer Alarm konfig0/1r2,(1)x x 17491749ups action fan USV-Betrieb Lüfter0/1r2,(1)x

17501750ups action cooling USV Aktion Kühlung0/1r1,(2)x x 17511751ups action heating USV Aktion Heizung0/1r1,(2)x x 17521752ups action humidification USV Aktion Befeuchtung0/1r1,(2)x x 17531753ups action dehumidification USV Aktion Entfeuchtung0/1r1,(2)x x 17541754unit cooling Einheit Kühlung0/1r2,(1)x x 17551755unit heating Einheit Heizung0/1r2,(1)x x 17561756unit humidification Einheit Befeuchtung0/1r2,(1)x x 17571757unit dehumidification Einheit Entfeuchtung0/1r2,(1)x x 17781778Cold water request Kaltwasser Nachfrage0/1r2,(1)x x 17791779unit stopped by fire alarm Einheit ausgeschaltet durch Feueralarm0/1r2,(1)x x 17801780freeze circulation running K?ltekreislauf l?uft0/1r1,(2)x 17831783BMS stop2BMS Stop20/1maybe on/unit off rw

18001800DIN1DIN10/1inactive/active r2,(1)x x 18011801DIN2DIN20/1inactive/active r2,(1)x x 18021802DIN3DIN30/1inactive/active r2,(1)x x 18031803DIN4DIN40/1inactive/active r2,(1)x x 18041804DIN5DIN50/1inactive/active r2,(1)x x 18051805DIN6DIN60/1inactive/active r2,(1)x x 18061806DIN7DIN70/1inactive/active r2,(1)x x 18071807DIN8DIN80/1inactive/active r2,(1)x x 18081808DIN9DIN90/1inactive/active r2,(1)x x 18091809DIN10DIN100/1inactive/active r2,(1)x x 18101810DIN11DIN110/1inactive/active r2,(1)x x 18111811DIN12DIN120/1inactive/active r2,(1)x x 18121812DIN13DIN130/1inactive/active r2,(1)x x 18131813DIN14DIN140/1inactive/active r2,(1)x x 18141814DIN15DIN150/1inactive/active r2,(1)x x 18151815DIN16DIN160/1inactive/active r2,(1)x x 18161816DIN17DIN170/1inactive/active r2,(1)x x 18171817DIN18DIN180/1inactive/active r2,(1)x x 18181818DIN19DIN190/1inactive/active r2,(1)x x 18191819DIN20DIN200/1inactive/active r2,(1)x x 18201820DIN21DIN210/1inactive/active r2,(1)x x 18211821DIN22DIN220/1inactive/active r2,(1)x x 18221822DIN23DIN230/1inactive/active r2,(1)x x 18231823DIN24DIN240/1inactive/active r2,(1)x x 18241824DIN25DIN250/1inactive/active r2,(1)x x 18251825DIN26DIN260/1inactive/active r2,(1)x x 18261826DIN27DIN270/1inactive/active r2,(1)x x 18271827DIN28DIN280/1inactive/active r2,(1)x x 18281828DIN29DIN290/1inactive/active r2,(1)x x 18291829DIN30DIN300/1inactive/active r2,(1)x x

Stulz-Adr.MODBUS-

adr.Description Beschreibung Modbus range mapped meaning

BMS-

access

Modbus-

function C7000IOC

C7000IOC

Chiller

18301830DIN31DIN310/1inactive/active r2,(1)x x 18311831DIN32DIN320/1inactive/active r2,(1)x x 18321832DIN33DIN330/1inactive/active r2,(1)x x 18331833DIN34DIN340/1inactive/active r2,(1)x x 18341834DIN35DIN350/1inactive/active r2,(1)x x 18351835DIN36DIN360/1inactive/active r2,(1)x x 18361836DIN37DIN370/1inactive/active r2,(1)x x 18371837DIN38DIN380/1inactive/active r2,(1)x x 18381838DIN39DIN390/1inactive/active r2,(1)x x 18391839DIN40DIN400/1inactive/active r2,(1)x x 18401840DIN41DIN410/1inactive/active r2,(1)x x 18411841DIN42DIN420/1inactive/active r2,(1)x x 18421842DIN43DIN430/1inactive/active r2,(1)x x 18431843DOUT1DOUT10/1inactive/active r1,(2)x x 18441844DOUT2DOUT20/1inactive/active r1,(2)x x 18451845DOUT3DOUT30/1inactive/active r1,(2)x x 18461846DOUT4DOUT40/1inactive/active r1,(2)x x 18471847DOUT5DOUT50/1inactive/active r1,(2)x x 18481848DOUT6DOUT60/1inactive/active r1,(2)x x 18491849DOUT7DOUT70/1inactive/active r1,(2)x x 18501850DOUT8DOUT80/1inactive/active r1,(2)x x 18511851DOUT9DOUT90/1inactive/active r1,(2)x x 18521852DOUT10DOUT100/1inactive/active r1,(2)x x 18531853DOUT11DOUT110/1inactive/active r1,(2)x x 18541854DOUT12DOUT120/1inactive/active r1,(2)x x 18551855DOUT13DOUT130/1inactive/active r1,(2)x x 18561856DOUT14DOUT140/1inactive/active r1,(2)x x 18571857DOUT15DOUT150/1inactive/active r1,(2)x x 18581858DOUT16DOUT160/1inactive/active r1,(2)x x 18591859DOUT17DOUT170/1inactive/active r1,(2)x x 18601860DOUT18DOUT180/1inactive/active r1,(2)x x 18611861DOUT19DOUT190/1inactive/active r1,(2)x x 18621862DOUT20DOUT200/1inactive/active r1,(2)x x 18631863DOUT21DOUT210/1inactive/active r1,(2)x x 18641864DOUT22DOUT220/1inactive/active r1,(2)x x 18651865DOUT23DOUT230/1inactive/active r1,(2)x x 18661866DOUT24DOUT240/1inactive/active r1,(2)x x 18671867DOUT25DOUT250/1inactive/active r1,(2)x x 18681868DOUT26DOUT260/1inactive/active r1,(2)x x 18691869DOUT27DOUT270/1inactive/active r1,(2)x x 18701870DOUT28DOUT280/1inactive/active r1,(2)x x 18711871DOUT29DOUT290/1inactive/active r1,(2)x x 18721872DOUT30DOUT300/1inactive/active r1,(2)x x 18731873DOUT31DOUT310/1inactive/active r1,(2)x x 22002200airflow1Luftstrom10/1ok/alarm r2,(1)x

22012201airflow2Luftstrom20/1ok/alarm r2,(1)x

Stulz-Adr.MODBUS-

adr.Description Beschreibung Modbus range mapped meaning

BMS-

access

Modbus-

function C7000IOC

C7000IOC

Chiller

22022202airflow3Luftstrom30/1ok/alarm r2,(1)x

22032203highpressure1Hochdruck10/1ok/alarm r2,(1)x

22042204highpressure2Hochdruck20/1ok/alarm r2,(1)x

22062206water detector Wasserdetektor0/1ok/alarm r2,(1)x x 22072207Phasecheck Phasencheck0/1ok/alarm r2,(1)x x 22082208fire/smoke Feuer/Rauch0/1ok/alarm r2,(1)x x 22162216return air temp.too high alarm Rücklauf Lufttemp.zu hoch Alarm0/1ok/alarm r2,(1)x

22172217return air humid.too high alarm Rücklauf Luftfeucht.zu hoch Alarm0/1ok/alarm r2,(1)x

22182218supply air temp.too high alarm Versorgung Lufttemp.zu hoch Alarm0/1ok/alarm r2,(1)x

22192219supply air humid.too high alarm Versorgung Luftfeucht.zu hoch Alarm0/1ok/alarm r2,(1)x

22202220water temp.too high alarm Wassertemp.zu hoch Alarm0/1ok/alarm r2,(1)x x 22212221return air temp.too low alarm Rücklauf Lufttemp.zu niedrig Alarm0/1ok/alarm r2,(1)x

22222222return air humid.too low alarm Rücklauf Luftfeucht.zu niedrig Alarm0/1ok/alarm r2,(1)x

22232223supply air temp.too low alarm Versorgung Lufttemp.zu niedrig Alarm0/1ok/alarm r2,(1)x

22242224supply air humid.too low alarm Versorgung Luftfeucht.zu niedrig Alarm0/1ok/alarm r2,(1)x

22252225water temp.too low alarm Wassertemp.zu niedrig Alarm0/1ok/alarm r2,(1)x x 22842284limit;return air temp.too high common alarm Grenzwert;Rücklauf Lufttemp.zu hoch geme0/1r1,(2)x

22852285limit;return air temp.too low common alarm c Grenzwert;Rücklauf Lufttemp.zu niedrig gem0/1r2,(1)x

22862286limit;supply air temp.too high common alarm G renzwert;Versorgung Lufttemp.zu hoch gem0/1r2,(1)x

22872287limit;supply air temp.too low common alarm Grenzwert;Versorgung Lufttemp.zu niedrig g0/1r1,(2)x

22882288limit;water temp.too high common alarm con Grenzwert;Wassertemp.zu hoch gemeinsam0/1r1,(2)x x 22892289limit;water temp.too low common alarm conf Grenzwert;Wassertemp.zu niedrig gemeinsa0/1r1,(2)x x 22902290limit;return air humid.too high common alarm

Grenzwert;Rücklauf Luftfeucht.zu hoch gem0/1r1,(2)x

22912291limit;return air humid.too low common alarm G renzwert;Rücklauf Luftfeucht.zu niedrig ge0/1r1,(2)x

22922292limit;supply air humid.too high common alarm

Grenzwert;Versorgung Luftfeucht.zu hoch ge0/1r1,(2)x

22932293limit;supply air humid.too low common alarm Grenzwert;Versorgung Luftfeucht.zu niedrig0/1r2,(1)x

23002300sensor1config.active Sensor1Konfig.aktiv0/1r1,(2)x x 23012301sensor1limit alarm Sensor1Grenzwertalarm0/1ok/alarm r2,(1)x x 23022302sensor1defect alarm Sensor1St?rung Alarm0/1ok/alarm r2,(1)x x 23032303sensor1defect common alarm config Sensor1St?rung gemeinsamer Alarm konfig0/1r1,(2)x x 23042304sensor1limit common alarm config Sensor1Grenzwert gemeinsamer Alarm kon0/1r1,(2)x x 23052305sensor1manual operation active Sensor1manuelle Bedienung aktiv0/1r1,(2)x x 23062306sensor1bms value active Sensor1bms Wert aktiv0/1rw1,(2).5x

24002400sensor2config.active Sensor2Konfig.aktiv0/1r1,(2)x x 24012401sensor2limit alarm Sensor2Grenzwertalarm0/1ok/alarm r2,(1)x x 24022402sensor2defect alarm Sensor2St?rung Alarm0/1ok/alarm r2,(1)x x 24032403sensor2defect common alarm config Sensor2St?rung gemeinsamer Alarm konfig0/1r1,(2)x x 24042404sensor2limit common alarm config Sensor2Grenzwert gemeinsamer Alarm kon0/1r1,(2)x x 24052405sensor2manual operation active Sensor2manuelle Bedienung aktiv0/1r1,(2)x x 24062406sensor2bms value active Sensor2bms Wert aktiv0/1rw1,(2).5x

25002500sensor3config.active Sensor3Konfig.aktiv0/1r1,(2)x x 25012501sensor3limit alarm Sensor3Grenzwertalarm0/1ok/alarm r2,(1)x x 25022502sensor3defect alarm Sensor3St?rung Alarm0/1ok/alarm r2,(1)x x 25032503sensor3defect common alarm config Sensor3St?rung gemeinsamer Alarm konfig0/1r1,(2)x x 25042504sensor3limit common alarm config Sensor3Grenzwert gemeinsamer Alarm kon0/1r1,(2)x x 25052505sensor3manual operation active Sensor3manuelle Bedienung aktiv0/1r1,(2)x x

Stulz-Adr.MODBUS-

adr.Description Beschreibung Modbus range mapped meaning

BMS-

access

Modbus-

function C7000IOC

C7000IOC

Chiller

25062506sensor3bms value active Sensor3bms Wert aktiv0/1rw1,(2).5x

26002600sensor4config.active Sensor4Konfig.aktiv0/1r1,(2)x x 26012601sensor4limit alarm Sensor4Grenzwertalarm0/1ok/alarm r2,(1)x x 26022602sensor4defect alarm Sensor4St?rung Alarm0/1ok/alarm r2,(1)x x 26032603sensor4defect common alarm config Sensor4St?rung gemeinsamer Alarm konfig0/1r1,(2)x x 26042604sensor4limit common alarm config Sensor4Grenzwert gemeinsamer Alarm kon0/1r1,(2)x x 26052605sensor4manual operation active Sensor4manuelle Bedienung aktiv0/1r1,(2)x x 26062606sensor4bms value active Sensor4bms Wert aktiv0/1rw1,(2).5x

27002700sensor5config.active Sensor5Konfig.aktiv0/1r1,(2)x x 27012701sensor5limit alarm Sensor5Grenzwertalarm0/1ok/alarm r2,(1)x x 27022702sensor5defect alarm Sensor5St?rung Alarm0/1ok/alarm r2,(1)x x 27032703sensor5defect common alarm config Sensor5St?rung gemeinsamer Alarm konfig0/1r1,(2)x x 27042704sensor5limit common alarm config Sensor5Grenzwert gemeinsamer Alarm kon0/1r1,(2)x x 27052705sensor5manual operation active Sensor5manuelle Bedienung aktiv0/1r1,(2)x x 27062706sensor5bms value active Sensor5bms Wert aktiv0/1rw1,(2).5x

28002800sensor6config.active Sensor6Konfig.aktiv0/1r1,(2)x x 28012801sensor6limit alarm Sensor6Grenzwertalarm0/1ok/alarm r2,(1)x x 28022802sensor6defect alarm Sensor6St?rung Alarm0/1ok/alarm r2,(1)x x 28032803sensor6defect common alarm config Sensor6St?rung gemeinsamer Alarm konfig0/1r1,(2)x x 28042804sensor6limit common alarm config Sensor6Grenzwert gemeinsamer Alarm kon0/1r1,(2)x x 28052805sensor6manual operation active Sensor6manuelle Bedienung aktiv0/1r1,(2)x x 28062806sensor6bms value active Sensor6bms Wert aktiv0/1rw1,(2).5x

29002900sensor7config.active Sensor7Konfig.aktiv0/1r1,(2)x x 29012901sensor7limit alarm Sensor7Grenzwertalarm0/1ok/alarm r2,(1)x x 29022902sensor7defect alarm Sensor7St?rung Alarm0/1ok/alarm r2,(1)x x 29032903sensor7defect common alarm config Sensor7St?rung gemeinsamer Alarm konfig0/1r1,(2)x x 29042904sensor7limit common alarm config Sensor7Grenzwert gemeinsamer Alarm kon0/1r1,(2)x x 29052905sensor7manual operation active Sensor7manuelle Bedienung aktiv0/1r1,(2)x x 29062906sensor7bms value active Sensor7bms Wert aktiv0/1rw1,(2).5x

30003000sensor8config.active Sensor8Konfig.aktiv0/1r1,(2)x x 30013001sensor8limit alarm Sensor8Grenzwertalarm0/1ok/alarm r2,(1)x x 30023002sensor8defect alarm Sensor8St?rung Alarm0/1ok/alarm r2,(1)x x 30033003sensor8defect common alarm config Sensor8St?rung gemeinsamer Alarm konfig0/1r1,(2)x x 30043004sensor8limit common alarm config Sensor8Grenzwert gemeinsamer Alarm kon0/1r1,(2)x x 30053005sensor8manual operation active Sensor8manuelle Bedienung aktiv0/1r1,(2)x x 30063006sensor8bms value active Sensor8bms Wert aktiv0/1rw1,(2).5x

31003100sensor9config.active Sensor9Konfig.aktiv0/1r1,(2)x x 31013101sensor9limit alarm Sensor9Grenzwertalarm0/1ok/alarm r2,(1)x x 31023102sensor9defect alarm Sensor9St?rung Alarm0/1ok/alarm r2,(1)x x 31033103sensor9defect common alarm config Sensor9St?rung gemeinsamer Alarm konfig0/1r1,(2)x x 31043104sensor9limit common alarm config Sensor9Grenzwert gemeinsamer Alarm kon0/1r1,(2)x x 31053105sensor9manual operation active Sensor9manuelle Bedienung aktiv0/1r1,(2)x x 31063106sensor9bms value active Sensor9bms Wert aktiv0/1rw1,(2).5x

32003200sensor10config.active Sensor10Konfig.aktiv0/1r1,(2)x x 32013201sensor10limit alarm Sensor10Grenzwertalarm0/1ok/alarm r2,(1)x x 32023202sensor10defect alarm Sensor10St?rung Alarm0/1ok/alarm r2,(1)x x

Stulz-Adr.MODBUS-

adr.Description Beschreibung Modbus range mapped meaning

BMS-

access

Modbus-

function C7000IOC

C7000IOC

Chiller

32033203sensor10defect common alarm config Sensor10St?rung gemeinsamer Alarm konf0/1r1,(2)x x 32043204sensor10limit common alarm config Sensor10Grenzwert gemeinsamer Alarm ko0/1r1,(2)x x 32053205sensor10manual operation active Sensor10manuelle Bedienung aktiv0/1r1,(2)x x 32063206sensor10bms value active Sensor10bms Wert aktiv0/1rw1,(2).5x

33003300sensor11config.active Sensor11Konfig.aktiv0/1r1,(2)x x 33013301sensor11limit alarm Sensor11Grenzwertalarm0/1ok/alarm r2,(1)x x 33023302sensor11defect alarm Sensor11St?rung Alarm0/1ok/alarm r2,(1)x x 33033303sensor11defect common alarm config Sensor11St?rung gemeinsamer Alarm konf0/1r1,(2)x x 33043304sensor11limit common alarm config Sensor11Grenzwert gemeinsamer Alarm ko0/1r1,(2)x x 33053305sensor11manual operation active Sensor11manuelle Bedienung aktiv0/1r1,(2)x x 33063306sensor11bms value active Sensor11bms Wert aktiv0/1rw1,(2).5x

34003400sensor12config.active Sensor12Konfig.aktiv0/1r1,(2)x x 34013401sensor12limit alarm Sensor12Grenzwertalarm0/1ok/alarm r2,(1)x x 34023402sensor12defect alarm Sensor12St?rung Alarm0/1ok/alarm r2,(1)x x 34033403sensor12defect common alarm config Sensor12St?rung gemeinsamer Alarm konf0/1r1,(2)x x 34043404sensor12limit common alarm config Sensor12Grenzwert gemeinsamer Alarm ko0/1r1,(2)x x 34053405sensor12manual operation active Sensor12manuelle Bedienung aktiv0/1r1,(2)x x 34063406sensor12bms value active Sensor12bms Wert aktiv0/1rw1,(2).5x

35003500sensor13config.active Sensor13Konfig.aktiv0/1r1,(2)x x 35013501sensor13limit alarm Sensor13Grenzwertalarm0/1ok/alarm r2,(1)x x 35023502sensor13defect alarm Sensor13St?rung Alarm0/1ok/alarm r2,(1)x x 35033503sensor13defect common alarm config Sensor13St?rung gemeinsamer Alarm konf0/1r1,(2)x x 35043504sensor13limit common alarm config Sensor13Grenzwert gemeinsamer Alarm ko0/1r1,(2)x x 35053505sensor13manual operation active Sensor13manuelle Bedienung aktiv0/1r1,(2)x x 35063506sensor13bms value active Sensor13bms Wert aktiv0/1rw1,(2).5x

36003600sensor14config.active Sensor14Konfig.aktiv0/1r1,(2)x x 36013601sensor14limit alarm Sensor14Grenzwertalarm0/1ok/alarm r2,(1)x x 36023602sensor14defect alarm Sensor14St?rung Alarm0/1ok/alarm r2,(1)x x 36033603sensor14defect common alarm config Sensor14St?rung gemeinsamer Alarm konf0/1r1,(2)x x 36043604sensor14limit common alarm config Sensor14Grenzwert gemeinsamer Alarm ko0/1r1,(2)x x 36053605sensor14manual operation active Sensor14manuelle Bedienung aktiv0/1r1,(2)x x 36063606sensor14bms value active Sensor14bms Wert aktiv0/1rw1,(2).5x

37003700sensor15config.active Sensor15Konfig.aktiv0/1r1,(2)x x 37013701sensor15limit alarm Sensor15Grenzwertalarm0/1ok/alarm r2,(1)x x 37023702sensor15defect alarm Sensor15St?rung Alarm0/1ok/alarm r2,(1)x x 37033703sensor15defect common alarm config Sensor15St?rung gemeinsamer Alarm konf0/1r1,(2)x x 37043704sensor15limit common alarm config Sensor15Grenzwert gemeinsamer Alarm ko0/1r1,(2)x x 37053705sensor15manual operation active Sensor15manuelle Bedienung aktiv0/1r1,(2)x x 37063706sensor15bms value active Sensor15bms Wert aktiv0/1rw1,(2).5x

38003800sensor16config.active Sensor16Konfig.aktiv0/1r1,(2)x x 38013801sensor16limit alarm Sensor16Grenzwertalarm0/1ok/alarm r2,(1)x x 38023802sensor16defect alarm Sensor16St?rung Alarm0/1ok/alarm r2,(1)x x 38033803sensor16defect common alarm config Sensor16St?rung gemeinsamer Alarm konf0/1r1,(2)x x 38043804sensor16limit common alarm config Sensor16Grenzwert gemeinsamer Alarm ko0/1r1,(2)x x 38053805sensor16manual operation active Sensor16manuelle Bedienung aktiv0/1r1,(2)x x 38063806sensor16bms value active Sensor16bms Wert aktiv0/1rw1,(2).5x

Stulz-Adr.MODBUS-

adr.Description Beschreibung Modbus range mapped meaning

BMS-

access

Modbus-

function C7000IOC

C7000IOC

Chiller

39003900sensor17config.active Sensor17Konfig.aktiv0/1r1,(2)x x 39013901sensor17limit alarm Sensor17Grenzwertalarm0/1ok/alarm r2,(1)x x 39023902sensor17defect alarm Sensor17St?rung Alarm0/1ok/alarm r2,(1)x x 39033903sensor17defect common alarm config Sensor17St?rung gemeinsamer Alarm konf0/1r1,(2)x x 39043904sensor17limit common alarm config Sensor17Grenzwert gemeinsamer Alarm ko0/1r1,(2)x x 39053905sensor17manual operation active Sensor17manuelle Bedienung aktiv0/1r1,(2)x x 39063906sensor17bms value active Sensor17bms Wert aktiv0/1rw1,(2).5x

40004000sensor18config.active Sensor18Konfig.aktiv0/1r1,(2)x x 40014001sensor18limit alarm Sensor18Grenzwertalarm0/1ok/alarm r2,(1)x x 40024002sensor18defect alarm Sensor18St?rung Alarm0/1ok/alarm r2,(1)x x 40034003sensor18defect common alarm config Sensor18St?rung gemeinsamer Alarm konf0/1r1,(2)x x 40044004sensor18limit common alarm config Sensor18Grenzwert gemeinsamer Alarm ko0/1r1,(2)x x 40054005sensor18manual operation active Sensor18manuelle Bedienung aktiv0/1r1,(2)x x 40064006sensor18bms value active Sensor18bms Wert aktiv0/1rw1,(2).5x

41004100sensor19config.active Sensor19Konfig.aktiv0/1r1,(2)x x 41014101sensor19limit alarm Sensor19Grenzwertalarm0/1ok/alarm r2,(1)x x 41024102sensor19defect alarm Sensor19St?rung Alarm0/1ok/alarm r2,(1)x x 41034103sensor19defect common alarm config Sensor19St?rung gemeinsamer Alarm konf0/1r1,(2)x x 41044104sensor19limit common alarm config Sensor19Grenzwert gemeinsamer Alarm ko0/1r1,(2)x x 41054105sensor19manual operation active Sensor19manuelle Bedienung aktiv0/1r1,(2)x x 41064106sensor19bms value active Sensor19bms Wert aktiv0/1rw1,(2).5x

42004200sensor20config.active Sensor20Konfig.aktiv0/1r1,(2)x x 42014201sensor20limit alarm Sensor20Grenzwertalarm0/1ok/alarm r2,(1)x x 42024202sensor20defect alarm Sensor20St?rung Alarm0/1ok/alarm r2,(1)x x 42034203sensor20defect common alarm config Sensor20St?rung gemeinsamer Alarm konfi0/1r1,(2)x x 42044204sensor20limit common alarm config Sensor20Grenzwert gemeinsamer Alarm ko0/1r1,(2)x x 42054205sensor20manual operation active Sensor20manuelle Bedienung aktiv0/1r1,(2)x x 42064206sensor20bms value active Sensor20bms Wert aktiv0/1rw1,(2).5x

43004300sensor21config.active Sensor21Konfig.aktiv0/1r1,(2)x x 43014301sensor21limit alarm Sensor21Grenzwertalarm0/1ok/alarm r2,(1)x x 43024302sensor21defect alarm Sensor21St?rung Alarm0/1ok/alarm r2,(1)x x 43034303sensor21defect common alarm config Sensor21St?rung gemeinsamer Alarm konfi0/1r1,(2)x x 43044304sensor21limit common alarm config Sensor21Grenzwert gemeinsamer Alarm ko0/1r1,(2)x x 43054305sensor21manual operation active Sensor21manuelle Bedienung aktiv0/1r1,(2)x x 43064306sensor21bms value active Sensor21bms Wert aktiv0/1rw1,(2).5x

44004400compressor1config.active Kompressor1Konfig.aktiv0/1r1,(2)x x 44014401compr.1manual operation active Kompr.1manuelle Bedienung aktiv0/1rw1,(2),5x x 44024402compr.1manual operation state Kompr.1manueller Bedienstatus0/1rw1,(2),5x x 44034403compr.1running Kompr.1l?uft0/1r2,(1)x x 44044404compr.1alarm Kompr.1Alarm0/1ok/alarm r2,(1)x

44054405compr.1low press.Alarm Kompr.1Niedrigdruck Alarm0/1ok/alarm r2,(1)x

44064406compr.1economizer active Kompr.1economizer Aktiv0/1r1,(2)CC2 44074407compr.1common alarm config Kompr.1gemeinsamer Alarm konfig0/1r1,(2)x

44084408compr.1low http://biz.doczj.com/doc/3d18263053.html,mon alarm config Kompr.1Niedrigdruck gemeinsamer Alarm k0/1r1,(2)x

45004500compressor2config.active Kompressor2Konfig.aktiv0/1r1,(2)x x 45014501compr.2manual operation active Kompr.2manuelle Bedienung aktiv0/1rw1,(2),5x x

Stulz-Adr.MODBUS-

adr.Description Beschreibung Modbus range mapped meaning

BMS-

access

Modbus-

function C7000IOC

C7000IOC

Chiller

45024502compr.2manual operation state Kompr.2manueller Bedienstatus0/1rw1,(2),5x x 45034503compr.2running Kompr.2l?uft0/1r2,(1)x x 45044504compr.2alarm Kompr.2Alarm0/1ok/alarm r2,(1)x

45054505compr.2low press.Alarm Kompr.2Niedrigdruck Alarm0/1ok/alarm r2,(1)x

45064506compr.2economizer active Kompr.2economizer Aktiv0/1r1,(2)CC2 45074507compr.2common alarm config Kompr.2gemeinsamer Alarm konfig0/1r1,(2)x

45084508compr.2low http://biz.doczj.com/doc/3d18263053.html,mon alarm config Kompr.2Niedrigdruck gemeinsamer Alarm k0/1r1,(2)x

46004600suctionvalve1config.Active Ansaugventil1Konfig.aktiv0/1r1,(2)x

46014601suctionvalve1manual operation active Ansaugventil1manuelle Bedienung aktiv0/1rw1,(2),5x

47004700suctionvalve2config.Active Ansaugventil2Konfig.aktiv0/1r1,(2)x

47014701suctionvalve2manual operation active Ansaugventil2manuelle Bedienung aktiv0/1rw1,(2),5x

48004800elec.-heating1config active elektr.Heizung1Konfig aktiv0/1r1,(2)x

48014801elec.-heating1manual operation active elektr.Heizung1manuelle Bedienung aktiv0/1rw1,(2),5x

48024802elec.-heating1alarm elektr.Heizung1Alarm0/1r2,(1)x

48034803elec.-heating1running elektr.Heizung1l?uft0/1r2,(1)x

48044804elec.-heating1manual operation running elektr.Heizung1manuelle Bedienung l?uft0/1rw1,(2),5x

48054805elec.-heating1common alarm config elektr.Heizung1gemeinsamer Alarm konfig0/1r1,(2)x

49004900elec.-heating2config active elektr.Heizung2Konfig.aktiv0/1r1,(2)x

49014901elec.-heating2manual operation active elektr.Heizung2manuelle Bedienung aktiv0/1rw1,(2),5x

49024902elec.-heating2alarm elektr.Heizung2Alarm0/1r2,(1)x

49034903elec.-heating2running elektr.Heizung2l?uft0/1r2,(1)x

49044904elec.-heating2manual operation running elektr.Heizung2manuelle Bedienung l?uft0/1rw1,(2),5x

49054905elec.-heating2common alarm config elektr.Heizung2gemeinsamer Alarm konfig0/1r1,(2)x

50005000elec.-heating3config active elektr.Heizung3Konfig.aktiv0/1r1,(2)x

50015001elec.-heating3manual operation active elektr.Heizung3manuelle Bedienung aktiv0/1rw1,(2),5x

50025002elec.-heating3alarm elektr.Heizung3Alarm0/1r2,(1)x

50035003elec.-heating3running elektr.Heizung3l?uft0/1r2,(1)x

50045004elec.-heating3manual operation running elektr.Heizung3manuelle Bedienung l?uft0/1rw1,(2),5x

50055005elec.-heating3common alarm config elektr.Heizung3gemeinsamer Alarm konfig0/1r1,(2)x

51005100elec.-heating4config active elektr.Heizung4Konfig.aktiv0/1r1,(2)x

51015101elec.-heating4manual operation active elektr.Heizung4manuelle Bedienung aktiv0/1rw1,(2),5x

51025102elec.-heating4alarm elektr.Heizung4Alarm0/1r2,(1)x

51035103elec.-heating4running elektr.Heizung4l?uft0/1r2,(1)x

51045104elec.-heating4manual operation running elektr.Heizung4manuelle Bedienung l?uft0/1rw1,(2),5x

51055105elec.-heating4common alarm config elektr.Heizung4gemeinsamer Alarm konfig0/1r1,(2)x

52005200GE/CW-valve config active GE/CW-Ventil Konfig.aktiv0/1r1,(2)x x 52015201GE/CW-valve manual operation active GE/CW-Ventil manuelle Bedienung aktiv0/1rw1,(2),5x x 52025202GE/CW-valve close with compr.-start GE/CW-Ventil schliessen mit Kompr.-start0/1r1,(2)x

52035203GE/CW-valve close if WT over SP GE/CW-Ventil schliessen wenn WTüber SP0/1r1,(2)x

52045204GE/CW-valve heating permitted GE/CW-Ventil Heizung erlaubt0/1r1,(2)x

52055205GE/CW-valve analog output inverted GE/CW-Ventil analoger Output vertauscht0/1r1,(2)x x 52065206GE/CW-valve maximum CW GE/CW-Ventil Maximum CW0/1rw1,(2),5x

53005300G-valve1config active G-Ventil1Konfig.aktiv0/1r1,(2)x x 53015301G-valve1manual operation active G-Ventil1manuelle Bedienung aktiv0/1rw1,(2),5x x 53505350G-valve2config active G-Ventil2Konfig.aktiv0/1r1,(2)x

53515351G-valve2manual operation active G-Ventil2manuelle Bedienung aktiv0/1rw1,(2),5x

Stulz-Adr.MODBUS-

adr.Description Beschreibung Modbus range mapped meaning

BMS-

access

Modbus-

function C7000IOC

C7000IOC

Chiller

54005400drycooler1config active Trockenkühler1Konfig.aktiv0/1r1,(2)x x 54015401drycooler1manual operation active Trockenkühler1manuelle Bedienung aktiv0/1rw1,(2),5x x 54025402drycooler1running Trockenkühler1l?uft0/1r2,(1)x x 54035403drycooler1alarm Trockenkühler1Alarm0/1r2,(1)x x 54045404drycooler1manual operation running Trockenkühler1manuelle Bedienung l?uft0/1rw1,(2),5x

54055405drycooler1common alarm config Trockenkühler1gemeinsamer Alarm konfig0/1r1,(2)x x 55005500drycooler2config active Trockenkühler2Konfig.aktiv0/1r1,(2)x

55015501drycooler2manual operation active Trockenkühler2manuelle Bedienung aktiv0/1rw1,(2),5x

55025502drycooler2running Trockenkühler2l?uft0/1r2,(1)x

55035503drycooler2alarm Trockenkühler2Alarm0/1r2,(1)x

55045504drycooler2manual operation running Trockenkühler2manuelle Bedienung l?uft0/1rw1,(2),5x

55055505drycooler2common alarm config Trockenkühler2gemeinsamer Alarm konfig0/1r1,(2)x

56005600drycooler3config active Trockenkühler3Konfig.aktiv0/1r1,(2)x

56015601drycooler3manual operation active Trockenkühler3manuelle Bedienung aktiv0/1rw1,(2),5x

56025602drycooler3running Trockenkühler3l?uft0/1r2,(1)x

56035603drycooler3alarm Trockenkühler3Alarm0/1r2,(1)x

56045604drycooler3manual operation running Trockenkühler3manuelle Bedienung l?uft0/1rw1,(2),5x

56055605drycooler3common alarm config Trockenkühler3gemeinsamer Alarm konfig0/1r1,(2)x

57005700drycooler4config active Trockenkühler4Konfig.aktiv0/1r1,(2)x

57015701drycooler4manual operation active Trockenkühler4manuelle Bedienung aktiv0/1rw1,(2),5x

57025702drycooler4running Trockenkühler4l?uft0/1r2,(1)x

57035703drycooler4alarm Trockenkühler4Alarm0/1r2,(1)x

57045704drycooler4manual operation running Trockenkühler4manuelle Bedienung l?uft0/1rw1,(2),5x

57055705drycooler4common alarm config Trockenkühler4gemeinsamer Alarm konfig0/1r1,(2)x

58005800pump1config active Pumpe1Konfig.aktiv0/1r1,(2)x x 58015801pump1manual operation active Pumpe1manuelle Bedienung aktiv0/1rw1,(2),5x x 58025802pump1running Pumpe1l?uft0/1r2,(1)x x 58035803pump1alarm Pumpe1Alarm0/1r2,(1)x x 58045804pump1common alarm config Pumpe1gemeinsamer Alarm konfig0/1r1,(2)x x 58055805pump1manual operation running Pumpe1manuelle Bedienung l?uft0/1r1,(2)x x 59005900pump2config active Pumpe2Konfig.aktiv0/1r1,(2)x x 59015901pump2manual operation active Pumpe2manuelle Bedienung aktiv0/1rw1,(2),5x x 59025902pump2running Pumpe2l?uft0/1r2,(1)x x 59035903pump2alarm Pumpe2Alarm0/1r2,(1)x x 59045904pump2common alarm config Pumpe2gemeinsamer Alarm konfig0/1r1,(2)x x 59055905pump2manual operation running Pumpe2manuelle Bedienung l?uft0/1r1,(2)x x 60006000pump3config active Pumpe3Konfig.aktiv0/1r1,(2)x x 60016001pump3manual operation active Pumpe3manuelle Bedienung aktiv0/1rw1,(2),5x x 60026002pump3running Pumpe3l?uft0/1r2,(1)x x 60036003pump3alarm Pumpe3Alarm0/1r2,(1)x x 60046004pump3common alarm config Pumpe3gemeinsamer Alarm konfig0/1r1,(2)x x 60056005pump3manual operation running Pumpe3manuelle Bedienung l?uft0/1r1,(2)x x 61006100pump4config active Pumpe4Konfig.aktiv0/1r1,(2)x x 61016101pump4manual operation active Pumpe4manuelle Bedienung aktiv0/1rw1,(2),5x x 61026102pump4running Pumpe4l?uft0/1r2,(1)x x 61036103pump4alarm Pumpe4Alarm0/1r2,(1)x x

Stulz-Adr.MODBUS-

adr.Description Beschreibung Modbus range mapped meaning

BMS-

access

Modbus-

function C7000IOC

C7000IOC

Chiller

61046104pump4common alarm config Pumpe4gemeinsamer Alarm konfig0/1r1,(2)x x 61056105pump4manual operation running Pumpe4manuelle Bedienung l?uft0/1r1,(2)x x 62006200hotgas-heating config active Heissgas-Heizung Konfig.aktiv0/1r1,(2)x

62016201hotgas-heating manual operation active Heissgas-Heizung manuelle Bedienung aktiv0/1rw1,(2),5x

62026202hotgas-heating running Heissgas-Heizung l?uft0/1r2,(1)x

62036203hotgas-heating manual operation running Heissgas-Heizung manuelle Bedienung l?uft0/1rw1,(2),5x

62056205hotgas-heating common alarm config Heissgas-Heizung gemeinsamer Alarm konfig0/1r1,(2)x

63006300PWW-heating config active PWW-Heizung Konfig.aktiv0/1r1,(2)x

63016301PWW-heating manual operation active PWW-Heizung manuelle Bedienung aktiv0/1rw1,(2),5x

63026302PWW-heating running PWW-Heizung l?uft0/1r2,(1)x

63036303PWW-heating manual operation running PWW-Heizung manuelle Bedienung l?uft0/1rw1,(2),5x

64006400humidifier1config active Befeuchter1Konfig.aktiv0/1r1,(2)x

64016401humidifier1manual operation active Befeuchter1manuelle Bedienung aktiv0/1rw1,(2),5x

64026402humidifier1running Befeuchter1l?uft0/1r2,(1)x

64036403humidifier1alarm Befeuchter1Alarm0/1r2,(1)x

64046404humidifier1manual operation running Befeuchter1manuelle Bedienung l?uft0/1rw1,(2),5x

64056405humidifier1common alarm config Befeuchter1gemeinsamer Alarm konfig0/1r1,(2)x

64066406humidifier1conductivity config Befeuchter1Leitf?higkeit konfig0/1r1,(2)x

64076407humidifier15uS common alarm config Befeuchter15uS gemeinsamer Alarm konfig0/1r1,(2)x

64086408humidifier120uS common alarm config Befeuchter120uS gemeinsamer Alarm konfi0/1r1,(2)x

64096409humidifier1alarm5uS Befeuchter1Alarm5uS0/1r1,(2)x

64106410humidifier1alarm20uS Befeuchter1Alarm20uS0/1r1,(2)x

64116411humidifier1drain valve manual operation activ

Befeuchter1Entleerungsventil manuelle Bedi0/1rw1,(2),5x

64126412humidifier1drain valve opened Befeuchter1Entleerungsventil ge?ffnet0/1r2,(1)x

64136413humidifier1drain valve manual operation statu

Befeuchter1Entleerungsventil manuelle Bedi0/1rw1,(2),5x

65006500humidifier2config active Befeuchter2Konfig.aktiv0/1r1,(2)x

65016501humidifier2manual operation active Befeuchter2manuelle Bedienung aktiv0/1rw1,(2),5x

65026502humidifier2running Befeuchter2l?uft0/1r2,(1)x

65036503humidifier2alarm Befeuchter2Alarm0/1r2,(1)x

65046504humidifier2manual operation running Befeuchter2manuelle Bedienung l?uft0/1rw1,(2),5x

65056505humidifier2common alarm config Befeuchter2gemeinsamer Alarm konfig0/1r1,(2)x

65066506humidifier2conductivity config Befeuchter2Leitf?higkeit konfig.0/1r1,(2)x

65076507humidifier25uS common alarm config Befeuchter25uS gemeinsamer Alarm konfig0/1r1,(2)x

65086508humidifier220uS common alarm config Befeuchter220uS gemeinsamer Alarm konfig0/1r1,(2)x

65096509humidifier2alarm5uS Befeuchter2Alarm5uS0/1r1,(2)x

65106510humidifier2alarm20uS Befeuchter2Alarm20uS0/1r1,(2)x

65116511humidifier2drain valve manual operation activ

Befeuchter2Entleerungsventil manuelle Bedi0/1rw1,(2),5x

65126512humidifier2drain valve opened Befeuchter2Entleerungsventil ge?ffnet0/1r2,(1)x

65136513humidifier2drain valve manual operation statu

Befeuchter2Entleerungsventil manuelle Bedi0/1rw1,(2),5x

66006600humidifier3config active Befeuchter3Konfig.aktiv0/1r1,(2)x

66016601humidifier3manual operation active Befeuchter3manuelle Bedienung aktiv0/1rw1,(2),5x

66026602humidifier3running Befeuchter3l?uft0/1r2,(1)x

66036603humidifier3alarm Befeuchter3Alarm0/1r2,(1)x

66046604humidifier3manual operation running Befeuchter3manuelle Bedienung l?uft0/1rw1,(2),5x

66056605humidifier3common alarm config Befeuchter3gemeinsamer Alarm konfig0/1r1,(2)x

66066606humidifier3conductivity config Befeuchter3Leitf?higkeit konfig.0/1r1,(2)x

Stulz-Adr.MODBUS-

adr.Description Beschreibung Modbus range mapped meaning

BMS-

access

Modbus-

function C7000IOC

C7000IOC

Chiller

66076607humidifier35uS common alarm config Befeuchter35uS gemeinsamer Alarm konfig0/1r1,(2)x 66086608humidifier320uS common alarm config Befeuchter320uS gemeinsamer Alarm konfig0/1r1,(2)x 66096609humidifier3alarm5uS Befeuchter3Alarm5uS0/1r1,(2)x 66106610humidifier3alarm20uS Befeuchter3Alarm20uS0/1r1,(2)x 66116611humidifier3drain valve manual operation activ

Befeuchter3Entleerungsventil manuelle Bedi0/1rw1,(2),5x 66126612humidifier3drain valve opened Befeuchter3Entleerungsventil ge?ffnet0/1r2,(1)x 66136613humidifier3drain valve manual operation statu

Befeuchter3Entleerungsventil manuelle Bedi0/1rw1,(2),5x 68006800dehumidification valve config active Entfeuchtung Ventil Konfig.aktiv0/1r1,(2)x 68016801dehumidification manual operation active Entfeuchtung manuelle Bedienung aktiv0/1rw1,(2),5x 68026802dehumidification running Entfeuchtung l?uft0/1r2,(1)x 68046804dehumidification manual operation running Entfeuchtung manuelle Bedienung l?uft0/1rw1,(2),5x 68056805dehumidification hotgas bypass config active E ntfeuchtung Heissgas Bypass Konfig.aktiv0/1r1,(2)x 68066806dehumidification valve value Entfeuchtung Ventil Wert0/1active/inactive r1,(2)x 68076807dehumidification hotgasbypass value Entfeuchtung Heissgasbypass Wert0/1active/inactive r1,(2)x 69006900fan1config active Ventilator1Konfig.aktiv0/1r1,(2)x 69016901fan1manual operation active Ventilator1manuelle Bedienung aktiv0/1rw1,(2),5x 69026902fan1running Ventilator1l?uft0/1r2,(1)x 69036903fan1alarm Ventilator1Alarm0/1r2,(1)x 69046904fan1filter alarm Ventilator1Filter Alarm0/1r2,(1)x 69056905fan1manual operation running Ventilator1manuelle Bedienung l?uft0/1rw1,(2),5x 69066906fan1common alarm config Ventilator1gemeinsamer Alarm konfig0/1r1,(2)x 69076907fan1filter common alarm config Ventilator1Filter gemeinsamer Alarm konfig0/1r1,(2)x 69536953fan1stop if cooling not possible Ventilator1Stopp,wenn Kühlen nicht m?glich0/1r1,(2)x 70007000fan2config active Ventilator2Konfig.aktiv0/1r1,(2)x 70017001fan2manual operation active Ventilator2manuelle Bedienung aktiv0/1rw1,(2),5x 70027002fan2running Ventilator2l?uft0/1r2,(1)x 70037003fan2alarm Ventilator2Alarm0/1r2,(1)x 70047004fan2filter alarm Ventilator2Filter Alarm0/1r2,(1)x 70057005fan2manual operation running Ventilator2manuelle Bedienung l?uft0/1rw1,(2),5x 70067006fan2common alarm config Ventilator2gemeinsamer Alarm konfig0/1r1,(2)x 70077007fan2filter common alarm config Ventilator2Filter gemeinsamer Alarm konfig0/1r1,(2)x 70537053fan2stop if cooling not possible Ventilator2Stopp,wenn Kühlen nicht m?glich0/1r1,(2)x 71007100fan3config active Ventilator3Konfig.aktiv0/1r1,(2)x 71017101fan3manual operation active Ventilator3manuelle Bedienung aktiv0/1rw1,(2),5x 71027102fan3running Ventilator3l?uft0/1r2,(1)x 71037103fan3alarm Ventilator3Alarm0/1r2,(1)x 71047104fan3filter alarm Ventilator3Filter Alarm0/1r2,(1)x 71057105fan3manual operation running Ventilator3manuelle Bedienung l?uft0/1rw1,(2),5x 71067106fan3common alarm config Ventilator3gemeinsamer Alarm konfig0/1r1,(2)x 71077107fan3filter common alarm config Ventilator3filter gemeinsamer Alarm konfig0/1r1,(2)x 71537153fan3stop if cooling not possible Ventilator3Stopp,wenn Kühlen nicht m?glich0/1r1,(2)x 72007200louver1config active Luftklappe1Konfig.aktiv0/1r1,(2)x 72017201louver1manual operation active Luftklappe1manuelle Bedienung aktiv0/1rw1,(2),5x 72027202louver1open Luftklappe1offen0/1close/open r2,(1)x 72037203louver1manual operation open Luftklappe1manuelle Bedienung offen0/1rw1,(2),5x 73007300louver2config active Luftklappe2Konfig.aktiv0/1r1,(2)x

Stulz-Adr.MODBUS-

adr.Description Beschreibung Modbus range mapped meaning

BMS-

access

Modbus-

function C7000IOC

C7000IOC

Chiller

73017301louver2manual operation active Luftklappe2manuelle Bedienung aktiv0/1rw1,(2),5x

73027302louver2open Luftklappe2offen0/1r2,(1)x

73037303louver2manual operation open Luftklappe2manuelle Bedienung offen0/1rw1,(2),5x

74007400louver3config active Luftklappe3Konfig.aktiv0/1r1,(2)x

74017401louver3manual operation active Luftklappe3manuelle Bedienung aktiv0/1rw1,(2),5x

74027402louver3open Luftklappe3offen0/1r2,(1)x

74037403louver3manual operation open Luftklappe3manuelle Bedienung offen0/1rw1,(2),5x

75007500ext.alarm config active1ext.Alarm konfig aktiv10/1r1,(2)x x 75017501ext.alarm manual operation enable1ext.Alarm manuelle Bedienung aktivieren10/1r1,(2)x x 75027502ext.alarm active1ext.Alarm aktiv10/1r2,(1)x x 75037503ext.alarm manual operation active1ext.Alarm manuelle Bedienung aktiv10/1r1,(2)x x 75047504ext.Alarm1common alarm config ext.Alarm1gemeinsamer Alarm konfig0/1r1,(2)x x 76007600ext.alarm config active2ext.Alarm konfig aktiv20/1r1,(2)x x 76017601ext.alarm manual operation enable2ext.Alarm manuelle Bedienung aktivieren20/1r1,(2)x x 76027602ext.alarm active2ext.Alarm aktiv20/1r2,(1)x x 76037603ext.alarm manual operation active2ext.Alarm manuelle Bedienung aktiv20/1r1,(2)x x 76047604ext.alarm2common alarm config ext.Alarm2gemeinsamer Alarm konfig0/1r1,(2)x x 77007700ext.alarm config active3ext.Alarm konfig aktiv30/1r1,(2)x x 77017701ext.alarm manual operation enable3ext.Alarm manuelle Bedienung aktivieren30/1r1,(2)x x 77027702ext.alarm active3ext.Alarm aktiv30/1r2,(1)x x 77037703ext.alarm manual operation active3ext.Alarm manuelle Bedienung aktiv30/1r1,(2)x x 77047704ext.alarm3common alarm config ext.Alarm3gemeinsamer Alarm konfig0/1r1,(2)x x 78007800ext.alarm config active4ext.Alarm konfig aktiv40/1r1,(2)x x 78017801ext.alarm manual operation enable4ext.Alarm manuelle Bedienung aktivieren40/1r1,(2)x x 78027802ext.alarm active4ext.Alarm aktiv40/1r2,(1)x x 78037803ext.alarm manual operation active4ext.Alarm manuelle Bedienung aktiv40/1r1,(2)x x 78047804ext.alarm4common alarm config ext.Alarm4gemeinsamer Alarm konfig0/1r1,(2)x x 79007900ext.alarm config active5ext.Alarm konfig aktiv50/1r1,(2)x x 79017901ext.alarm manual operation enable5ext.Alarm manuelle Bedienung aktivieren50/1r1,(2)x x 79027902ext.alarm active5ext.Alarm aktiv50/1r2,(1)x x 79037903ext.alarm manual operation active5ext.Alarm manuelle Bedienung aktiv50/1r1,(2)x x 79047904ext.alarm5common alarm config ext.Alarm5gemeinsamer Alarm konfig0/1r1,(2)x x 80008000ext.alarm config active6ext.Alarm konfig aktiv60/1r1,(2)x x 80018001ext.alarm manual operation enable6ext.Alarm manuelle Bedienung aktivieren60/1r1,(2)x x 80028002ext.alarm active6ext.Alarm aktiv60/1r2,(1)x x 80038003ext.alarm manual operation active6ext.Alarm manuelle Bedienung aktiv60/1r1,(2)x x 80048004ext.alarm6common alarm config ext.Alarm6gemeinsamer Alarm konfig0/1r1,(2)x x 81008100ext.alarm config active7ext.Alarm konfig aktiv70/1r1,(2)x x 81018101ext.alarm manual operation enable7ext.Alarm manuelle Bedienung aktivieren70/1r1,(2)x x 81028102ext.alarm active7ext.Alarm aktiv70/1r2,(1)x x 81038103ext.alarm manual operation active7ext.Alarm manuelle Bedienung aktiv70/1r1,(2)x x 81048104ext.alarm7common alarm config ext.Alarm7gemeinsamer Alarm konfig0/1r1,(2)x x 82008200ext.alarm config active8ext.Alarm konfig aktiv80/1r1,(2)x x 82018201ext.alarm manual operation enable8ext.Alarm manuelle Bedienung aktivieren80/1r1,(2)x x 82028202ext.alarm active8ext.Alarm aktiv80/1r2,(1)x x 82038203ext.alarm manual operation active8ext.Alarm manuelle Bedienung aktiv80/1r1,(2)x x

Stulz-Adr.MODBUS-

adr.Description Beschreibung Modbus range mapped meaning

BMS-

access

Modbus-

function C7000IOC

C7000IOC

Chiller

82048204ext.alarm8common alarm config ext.Alarm8gemeinsamer Alarm konfig0/1r1,(2)x x 83008300ext.alarm config active9ext.Alarm konfig aktiv90/1r1,(2)x x 83018301ext.alarm manual operation enable9ext.Alarm manuelle Bedienung aktivieren90/1r1,(2)x x 83028302ext.alarm active9ext.Alarm aktiv90/1r2,(1)x x 83038303ext.alarm manual operation active9ext.Alarm manuelle Bedienung aktiv90/1r1,(2)x x 83048304ext.alarm9common alarm config ext.Alarm9gemeinsamer Alarm konfig0/1r1,(2)x x 84008400ext.alarm config active10ext.Alarm konfig aktiv100/1r1,(2)x x 84018401ext.alarm manual operation enable10ext.Alarm manuelle Bedienung aktivieren100/1r1,(2)x x 84028402ext.alarm active10ext.Alarm aktiv100/1r2,(1)x x 84038403ext.alarm manual operation active10ext.Alarm manuelle Bedienung aktiv100/1r1,(2)x x 84048404ext.alarm10common alarm config ext.Alarm10gemeinsamer Alarm konfig0/1r1,(2)x x 85008500airflow1Luftstrom10/1ok/alarm r1,2x

85018501airflow2Luftstrom20/1ok/alarm r1,2x

85028502airflow3Luftstrom30/1ok/alarm r1,2x

85038503highpressure1Hochdruck10/1ok/alarm r1,2x x 85048504highpressure2Hochdruck20/1ok/alarm r1,2x

85058505water detector Wasserdetektor0/1ok/alarm r1,2x x 85068506Phasecheck Phasencheck0/1ok/alarm r1,2x x 85078507fire/smoke Feuer/Rauch0/1ok/alarm r1,2x x 85088508return air temp.too high alarm Rücklauf Lufttemp.zu hoch Alarm0/1ok/alarm r1,2x

85098509return air humid.too high alarm Rücklauf Luftfeucht.zu hoch Alarm0/1ok/alarm r1,2x

85108510supply air temp.too high alarm Versorgung Lufttemp.zu hoch Alarm0/1ok/alarm r1,2x

85118511supply air humid.too high alarm Versorgung Luftfeucht.zu hoch Alarm0/1ok/alarm r1,2x

85128512water temp.too high alarm Wassertemp.zu hoch Alarm0/1ok/alarm r1,2x

85138513return air temp.too low alarm Rücklauf Lufttemp.zu niedrig Alarm0/1ok/alarm r1,2x

85148514return air humid.too low alarm Rücklauf Luftfeucht.zu niedrig Alarm0/1ok/alarm r1,2x

85158515supply air temp.too low alarm Versorgung Lufttemp.zu niedrig Alarm0/1ok/alarm r1,2x

85168516supply air humid.too low alarm Versorgung Luftfeucht.zu niedrig Alarm0/1ok/alarm r1,2x

85178517water temp.too low alarm Wassertemp.zu niedrig Alarm0/1ok/alarm r1,2x

85188518sensor1limit alarm Sensor1Grenzwertalarm0/1ok/alarm r1,2x x 85198519sensor2limit alarm Sensor2Grenzwertalarm0/1ok/alarm r1,2x x 85208520sensor3limit alarm Sensor3Grenzwertalarm0/1ok/alarm r1,2x x 85218521sensor4limit alarm Sensor4Grenzwertalarm0/1ok/alarm r1,2x x 85228522sensor5limit alarm Sensor5Grenzwertalarm0/1ok/alarm r1,2x x 85238523sensor6limit alarm Sensor6Grenzwertalarm0/1ok/alarm r1,2x x 85248524sensor7limit alarm Sensor7Grenzwertalarm0/1ok/alarm r1,2x x 85258525sensor8limit alarm Sensor8Grenzwertalarm0/1ok/alarm r1,2x x 85268526sensor9limit alarm Sensor9Grenzwertalarm0/1ok/alarm r1,2x x 85278527sensor10limit alarm Sensor10Grenzwertalarm0/1ok/alarm r1,2x x 85288528sensor11limit alarm Sensor11Grenzwertalarm0/1ok/alarm r1,2x x 85298529sensor12limit alarm Sensor12Grenzwertalarm0/1ok/alarm r1,2x x 85308530sensor13limit alarm Sensor13Grenzwertalarm0/1ok/alarm r1,2x x 85318531sensor14limit alarm Sensor14Grenzwertalarm0/1ok/alarm r1,2x x 85328532sensor15limit alarm Sensor15Grenzwertalarm0/1ok/alarm r1,2x x 85338533sensor16limit alarm Sensor16Grenzwertalarm0/1ok/alarm r1,2x x 85348534sensor17limit alarm Sensor17Grenzwertalarm0/1ok/alarm r1,2x x

Stulz-Adr.MODBUS-

adr.Description Beschreibung Modbus range mapped meaning

BMS-

access

Modbus-

function C7000IOC

C7000IOC

Chiller

85358535sensor18limit alarm Sensor18Grenzwertalarm0/1ok/alarm r1,2x x 85368536sensor19limit alarm Sensor19Grenzwertalarm0/1ok/alarm r1,2x x 85378537sensor20limit alarm Sensor20Grenzwertalarm0/1ok/alarm r1,2x x 85388538sensor21limit alarm Sensor21Grenzwertalarm0/1ok/alarm r1,2x x 85398539sensor1defect alarm Sensor1St?rung Alarm0/1ok/alarm r1,2x x 85408540sensor2defect alarm Sensor2St?rung Alarm0/1ok/alarm r1,2x x 85418541sensor3defect alarm Sensor3St?rung Alarm0/1ok/alarm r1,2x x 85428542sensor4defect alarm Sensor4St?rung Alarm0/1ok/alarm r1,2x x 85438543sensor5defect alarm Sensor5St?rung Alarm0/1ok/alarm r1,2x x 85448544sensor6defect alarm Sensor6St?rung Alarm0/1ok/alarm r1,2x x 85458545sensor7defect alarm Sensor7St?rung Alarm0/1ok/alarm r1,2x x 85468546sensor8defect alarm Sensor8St?rung Alarm0/1ok/alarm r1,2x x 85478547sensor9defect alarm Sensor9St?rung Alarm0/1ok/alarm r1,2x x 85488548sensor10defect alarm Sensor10St?rung Alarm0/1ok/alarm r1,2x x 85498549sensor11defect alarm Sensor11St?rung Alarm0/1ok/alarm r1,2x x 85508550sensor12defect alarm Sensor12St?rung Alarm0/1ok/alarm r1,2x x 85518551sensor13defect alarm Sensor13St?rung Alarm0/1ok/alarm r1,2x x 85528552sensor14defect alarm Sensor14St?rung Alarm0/1ok/alarm r1,2x x 85538553sensor15defect alarm Sensor15St?rung Alarm0/1ok/alarm r1,2x x 85548554sensor16defect alarm Sensor16St?rung Alarm0/1ok/alarm r1,2x x 85558555sensor17defect alarm Sensor17St?rung Alarm0/1ok/alarm r1,2x x 85568556sensor18defect alarm Sensor18St?rung Alarm0/1ok/alarm r1,2x x 85578557sensor19defect alarm Sensor19St?rung Alarm0/1ok/alarm r1,2x x 85588558sensor20defect alarm Sensor20St?rung Alarm0/1ok/alarm r1,2x x 85598559sensor21defect alarm Sensor21St?rung Alarm0/1ok/alarm r1,2x x 85608560compr.1alarm Kompr.1Alarm0/1ok/alarm r1,2x

85618561compr.2alarm Kompr.2Alarm0/1ok/alarm r1,2x

85628562low press.Alarm1Niedrigdruck Alarm10/1ok/alarm r1,2x x 85638563low press.Alarm2Niedrigdruck Alarm20/1ok/alarm r1,2x

85648564elec.-heating1alarm elektr.Heizung1Alarm0/1ok/alarm r1,2x

85658565elec.-heating2alarm elektr.Heizung2Alarm0/1ok/alarm r1,2x

85668566elec.-heating3alarm elektr.Heizung3Alarm0/1ok/alarm r1,2x

85678567elec.-heating4alarm elektr.Heizung4Alarm0/1ok/alarm r1,2x

85688568drycooler1alarm Trockenkühler1Alarm0/1ok/alarm r1,2x x 85698569drycooler2alarm Trockenkühler2Alarm0/1ok/alarm r1,2x

85708570drycooler3alarm Trockenkühler3Alarm0/1ok/alarm r1,2x

85718571drycooler4alarm Trockenkühler4Alarm0/1ok/alarm r1,2x

85728572pump1alarm Pumpe1Alarm0/1ok/alarm r1,2x x 85738573pump2alarm Pumpe2Alarm0/1ok/alarm r1,2x x 85748574pump3alarm Pumpe3Alarm0/1ok/alarm r1,2x x 85758575pump4alarm Pumpe4Alarm0/1ok/alarm r1,2x x 85768576humidifier1alarm Befeuchter1Alarm0/1ok/alarm r1,2x

85778577humidifier2alarm Befeuchter2Alarm0/1ok/alarm r1,2x

85788578humidifier3alarm Befeuchter3Alarm0/1ok/alarm r1,2x

85798579humidifier1alarm5uS Befeuchter1Alarm5uS0/1ok/alarm r1,2x

85808580humidifier2alarm5uS Befeuchter2Alarm5uS0/1ok/alarm r1,2x

Stulz-Adr.MODBUS-

adr.Description Beschreibung Modbus range mapped meaning

BMS-

access

Modbus-

function C7000IOC

C7000IOC

Chiller

85818581humidifier3alarm5uS Befeuchter3Alarm5uS0/1ok/alarm r1,2x

85828582humidifier1alarm20uS Befeuchter1Alarm20uS0/1ok/alarm r1,2x

85838583humidifier2alarm20uS Befeuchter2Alarm20uS0/1ok/alarm r1,2x

85848584humidifier3alarm20uS Befeuchter3Alarm20uS0/1ok/alarm r1,2x

85858585fan1alarm Ventilator1Alarm0/1ok/alarm r1,2x

85868586fan2alarm Ventilator2Alarm0/1ok/alarm r1,2x

85878587fan3alarm Ventilator3Alarm0/1ok/alarm r1,2x

85888588fan1filter alarm Ventilator1Filter Alarm0/1ok/alarm r1,2x

85898589fan2filter alarm Ventilator2Filter Alarm0/1ok/alarm r1,2x

85908590fan3filter alarm Ventilator3Filter Alarm0/1ok/alarm r1,2x

85918591ext.Alarm1active ext.Alarm1aktiv0/1ok/alarm r1,2x x 85928592ext.Alarm2active ext.Alarm2aktiv0/1ok/alarm r1,2x x 85938593ext.Alarm3active ext.Alarm3aktiv0/1ok/alarm r1,2x x 85948594ext.Alarm4active ext.Alarm4aktiv0/1ok/alarm r1,2x x 85958595ext.Alarm5active ext.Alarm5aktiv0/1ok/alarm r1,2x x 85968596ext.Alarm6active ext.Alarm6aktiv0/1ok/alarm r1,2x x 85978597ext.Alarm7active ext.Alarm7aktiv0/1ok/alarm r1,2x x 85988598ext.Alarm8active ext.Alarm8aktiv0/1ok/alarm r1,2x x 85998599ext.Alarm9active ext.Alarm9aktiv0/1ok/alarm r1,2x x 86008600ext.Alarm10active ext.Alarm10aktiv0/1ok/alarm r1,2x x 86018601hotgas-heating alarm Heissgas-Heizung Alarm0/1ok/alarm r1,2x

86028602eev1pressure sensor error eev1Drucksensor Fehler0/1ok/alarm r1,2x x 86038603eev1temperature sensor error eev1Temperatursensor Fehler0/1ok/alarm r1,2x x 86048604eev1stepper motor error eev1Schrittmotor Fehler0/1ok/alarm r1,2x x 86058605eev2pressure sensor error eev2Drucksensor Fehler0/1ok/alarm r1,2x x 86068606eev2temperature sensor error eev2Temperatursensor Fehler0/1ok/alarm r1,2x x 86078607eev2stepper motor error eev2Schrittmotor Fehler0/1ok/alarm r1,2x x 86088608waterflow failure Wasserfluss St?rung0/1ok/alarm r1,2x x 86098609Valve test alarm Ventiltest Alarm0/1ok/alarm r1,2x

86148614condenser1alarm Kondensator1Alarm0/1ok/alarm r2,(1)x

86158615condenser2alarm Kondensator2Alarm0/1ok/alarm r2,(1)x

86278627room high pressure alarm Raumhochdruck Alarm0/1ok/alarm r2,(1)x

86288628filter1alarm Filter1Alarm0/1ok/alarm r2,(1)x

86298629filter2alarm Filter2Alarm0/1ok/alarm r2,(1)x

86308630filter3alarm Filter3Alarm0/1ok/alarm r2,(1)x

86318631RC1circuit breaker tripped Kaeltekreis1Leitungsschutzschalter ausgel?0/1ok/alarm r1,2x 86328632RC2circuit breaker tripped Kaeltekreis2Leitungsschutzschalter ausgel?0/1ok/alarm r1,2CC2 86468646Moveable coil alarm Klappregister Alarm0/1ok/alarm r2,(1)

86488648External Filter alarm Externer Filter Alarm0/1ok/alarm r2,(1)

86498649water temp.inlet1too low alarm Wassertemp.Einlass1zu niedrig Alarm0/1ok/alarm r2,(1)x 86508650water temp.inlet1too high alarm Wassertemp.Einlass1zu hoch Alarm0/1ok/alarm r2,(1)x 86518651water temp.outlet1too low alarm Wassertemp.Auslass1zu niedrig Alarm0/1ok/alarm r2,(1)x 86528652water temp.outlet1too high alarm Wassertemp.Auslass1zu hoch Alarm0/1ok/alarm r2,(1)x 86538653water temp.inlet2too low alarm Wassertemp.Einlass2zu niedrig Alarm0/1ok/alarm r2,(1)x 86548654water temp.inlet2too high alarm Wassertemp.Einlass2zu hoch Alarm0/1ok/alarm r2,(1)x 86558655water temp.outlet2too low alarm Wassertemp.Auslass2zu niedrig Alarm0/1ok/alarm r2,(1)x

Stulz-Adr.MODBUS-

adr.Description Beschreibung Modbus range mapped meaning

BMS-

access

Modbus-

function C7000IOC

C7000IOC

Chiller

86568656water temp.outlet2too high alarm Wassertemp.Auslass2zu hoch Alarm0/1ok/alarm r2,(1)x 86578657eev1reliability alarm(Carel EVD)eev1Betriebssicherheit Alarm(Carel EVD)0/1ok/alarm r2,(1)CC2 86588658eev2reliability alarm(Carel EVD)eev2Betriebssicherheit Alarm(Carel EVD)0/1ok/alarm r2,(1)CC2 86798679state that shut off compressor included envelo

feststellen,dass Abschalten Kompresser enth0/1ok/alarm r2,(1)

86808680probe broken analog input b3,uPC DP18Sonde besch?digt analoger Input b3,uPC DP0/1ok/alarm r2,(1)

86818681probe broken analog input b4,uPC DP19Sonde besch?digt analoger Input b4,uPC DP0/1ok/alarm r2,(1)

86828682probe broken analog input b5,uPC DP20Sonde besch?digt analoger Input b5,uPC DP0/1ok/alarm r2,(1)

86838683probe broken analog input b6,uPC DP21Sonde besch?digt analoger Input b6,uPC DP0/1ok/alarm r2,(1)

86848684maximum discharge pressure,uPC DP23Maximaler Entlastungsdruck,uPC DP230/1ok/alarm r2,(1)

86858685minimum suction pressure,uPC DP24minimaler Ansaugdruck,uPC DP240/1ok/alarm r2,(1)

86868686discharge temperature alarm,uPC DP25Entlastungstemperatur Alarm,uPC DP250/1ok/alarm r2,(1)

86878687pressure difference lower than minimum,uPC Druckdifferenz unterhalb Minimum,uPC DP20/1ok/alarm r2,(1)

86888688compressor fails to start,uPC DP27Fehlstart Kompressor,uPC DP270/1ok/alarm r2,(1)

86898689compressor exceeds max time allowed workin

Kompressorüberschreitet die maximal erlaub0/1ok/alarm r2,(1)

86908690low super heat alarm ee valve,uPC DP29niedriger Super Hitze Alarm ee Ventil,uPC DP0/1ok/alarm r2,(1)

86918691mop alarm ee valve,uPC DP30mop Alarm ee Ventil,uPC DP300/1ok/alarm r2,(1)

86928692low suction temperature alarm ee valve,uPC n iedrige Ansaugtemperatur Alarm ee Ventil,u0/1ok/alarm r2,(1)

86938693evd evo evotunes alarm,uPC DP32evd evo evotunes Alarm,uPC DP320/1ok/alarm r2,(1)

86948694evd evo regulation alarms lop mop low sh low evd evo Regulierung Alarme lop mop niedrig0/1ok/alarm r2,(1)

86958695evd evo system alarms probe error,uPC DP3

evd evo System Alarme Sondenfehler,uPC D0/1ok/alarm r2,(1)

86968696general inverter alarm,uPC DP35allgemeiner Umrichter Alarm,uPC DP350/1ok/alarm r2,(1)

86978697communication loss with power inverter,uPC V erlust Kommunikation mit Strom-Umrichter,0/1ok/alarm r2,(1)

86988698Communication loss with icc controller Verlust Kommunikation mit icc Steuerung0/1ok/alarm r2,(1)

86998699inverter model not compatible with selected co

Inverter Model passt nicht zum gew?hlten Kom0/1ok/alarm r2,(1)

87008700eev1config active eev1Konfig.aktiv0/1r1,(2)x x 87018701eev1battery supply(Alco VCM)eev1Batterieversorgung(Alco VCM)0/1r1,(2)x x 87028702eev1MOP control(Alco VCM)eev1MOP Steuerung(Alco VCM)0/1off/on r2,(1)x x 87038703eev1superheat control mode(Alco VCM)eev1überhitzung Steuerungsmodus(Alco VC0/1mode0/mode1r2,(1)x x 87048704eev1manual operation eev1manuelle Bedienung0/1/active r1,(2)x x 87058705eev1pressure sensor error eev1Drucksensor Fehler0/1ok/alarm r1,(2)x x 87068706eev1temperature sensor error eev1Temperatursensor Fehler0/1ok/alarm r1,(2)x x 87078707eev1stepper motor error eev1Schrittmotor Fehler0/1ok/alarm r1,(2)x x 87088708eev1pressure sensor error common alarm co eev1Drucksensor Fehler gemeinsamer Alarm0/1rw1,(2)x x 87098709eev1temperature sensor error common alarm

eev1Temperatursensor Fehler gemeinsamer0/1rw1,(2)x x 87108710eev1stepper motor error common alarm conf eev1Schrittmotor Fehler gemeinsamer Alarm0/1rw1,(2)x x 87118711eev1reliability alarm(Carel EVD)eev1Betriebssicherheit Alarm(Carel EVD)0/1r2,(1)

87128712eev1reliability common alarm(Carel EVD)eev1Betriebssicherheit gemeinsamer Alarm0/1r1,(2)

88008800eev2config active eev2Konfig.aktiv0/1r1,(2)x x 88018801eev2battery supply eev2Batterieversorgung0/1r1,(2)x x 88028802eev2MOP control eev2MOP Steuerung0/1off/on r2,(1)x x 88038803eev2superheat control mode eev2überhitzung Steuerungsmodus0/1mode0/mode1r2,(1)x x 88048804eev2manual operation eev2manuelle Bedienung0/1/active r1,(2)x x 88058805eev2pressure sensor error eev2Drucksensor Fehler0/1ok/alarm r1,(2)x x 88068806eev2temperature sensor error eev2Temperatursensor Fehler0/1ok/alarm r1,(2)x x 88078807eev2stepper motor error eev2Schrittmotor Fehler0/1ok/alarm r1,(2)x x 88088808eev2pressure sensor error common alarm co eev2Drucksensor Fehler gemeinsamer Alarm0/1rw1,(2)x x

Stulz-Adr.MODBUS-

adr.Description Beschreibung Modbus range mapped meaning

BMS-

access

Modbus-

function C7000IOC

C7000IOC

Chiller

88098809eev2temperature sensor error common alarm

eev2Temperatursensor Fehler gemeinsamer0/1rw1,(2)x x 88108810eev2stepper motor error common alarm conf eev2Schrittmotor Fehler gemeinsamer Alarm0/1rw1,(2)x x 88118811eev2availability error alarm eev2Verfügbarkeit Fehler Alarm0/1r2,(1)

88128812eev2availability error common alarm eev2Verfügbarkeit Fehler gemeinsamer Alar0/1r1,(2)

89008900valout1config.Active valout1Konfig.aktiv0/1r1,(2)x x 90009000valout2config.Active valout2Konfig.aktiv0/1r1,(2)x x 91009100valout3config.Active valout3Konfig.aktiv0/1r1,(2)x x 92009200valout4config.Active valout4Konfig.aktiv0/1r1,(2)x x 93009300hgbp1config.active hgbp1Konfig.aktiv0/1r1,(2)x x 93019301hgbp1manual operation active hgbp1manuelle Bedienung aktiv0/1r1,(2)x x 94009400hgbp2config.active hgbp2Konfig.aktiv0/1r1,(2)x

94019401hgbp2manual operation active hgbp2manuelle Bedienung aktiv0/1r1,(2)x

95069506compr.3economizer active Kompr.3economizer Aktiv0/1r1,(2)CC2 95089508compr.low http://biz.doczj.com/doc/3d18263053.html,mon alarm config Kompr.Niedrigdruck gemeinsamer Alarm ko0/1r1,(2)

96069606compr.4economizer active Kompr.4economizer Aktiv0/1r1,(2)CC2 96089608compr.low http://biz.doczj.com/doc/3d18263053.html,mon alarm config Kompr.Niedrigdruck gemeinsamer Alarm ko0/1r1,(2)

97069706compr.5economizer active Kompr.5economizer Aktiv0/1r1,(2)CC2 97089708compr.low http://biz.doczj.com/doc/3d18263053.html,mon alarm config Kompr.Niedrigdruck gemeinsamer Alarm ko0/1r1,(2)

98069806compr.6economizer active Kompr.6economizer Aktiv0/1r1,(2)CC2 98089808compr.low http://biz.doczj.com/doc/3d18263053.html,mon alarm config Kompr.Niedrigdruck gemeinsamer Alarm ko0/1r1,(2)

99009900ECO louver config active ECO Luftklappe Konfig.aktiv0/1r1,(2)x

99019901ECO louver manual operation active ECO Luftklappe manuelle Bedienung aktiv0/1rw1,(2)x

99309930ECO-COOL2config active ECO-COOL2Konfig.aktiv0/1r1,(2)x 1000010000Moveable coil config active Klappregister Konfig.aktiv0/1r1,(2)x 1000110001Moveable coil enabled Klappregister aktiviert0/1r2,(1)x 1000210002Moveable coil direction Klappregister Richtung0/10:forth/1:back r2,(1)x 1000310003Moveable coil manual operation active Klappregister manuelle Bedienung aktiv0/1r1,(2)x 1000410004Moveable coil manual operation direction Klappregister manuelle Bedienung Richtung0/10:forth/1:back r1,(2)x 1000610006Moveable coil common alarm configured Klappregister gemeinsamer Alarm konfigurier0/1r1,(2)x 1010110101freecooling possible Freikühlung m?glich0/1no/yes r1,(2)x 1010210102freecooling drycooler possible Freikühlung Trockenkühler m?glich0/1no/yes r1,(2)x 1030010300AE control active AE Kontrolle aktiv0/1r1,(2)x 1030110301room high pressure alarm active Raumhochdruck Alarm aktiv0/1r2,(1)x 1030210302common alarm configured with room high pre gemeinsamer Alarm konfiguriert mit Raumho0/1r1,(2)x 1030310303force summer mode St?rke Sommermodus0/1inactive/active rw1,(2)x 1030410304action on humidity too high alarm Wirkung auf Feuchtigkeit zu hoch Alarm0/1rw1,(2)x 1030510305action on water alarm Wirkung auf Wasseralarm0/1rw1,(2)x 1040010400Fresh air louver config active Frischluftklappe Konfig.aktiv0/1r1,(2)x 1040110401Fresh air louver manual operation active Frischluftklappe manuelle Bedienung aktiv0/1rw1,(2),5x 1050010500Anti-freeze louver configuration active Frostschutzklappe Konfiguration aktiv0/1r1,(2)x 1050110501Anti-freeze louver manual operation active Frostschutzklappe manuelle Bedienung aktiv0/1rw1,(2),5x 1060010600Circulation louver configuration active Umluftklappe Konfiguration aktiv0/1r1,(2)x 1060110601Circulation louver manual operation active Umluftklappe manuelle Bedienung aktiv0/1rw1,(2),5x 1070010700Exit louver configuration active Fortluftklappe Konfiguration aktiv0/1r1,(2)x 1070110701Exit louver manual operation active Fortluftklappe manuelle Bedienung aktiv0/1rw1,(2),5x 1070210702Exit louver opening state Fortluftklappe?ffnungszustand0/1r2,(1)x

Stulz-Adr.MODBUS-

adr.Description Beschreibung Modbus range mapped meaning

BMS-

access

Modbus-

function C7000IOC

C7000IOC

Chiller

1070310703Exit louver manual operation opening state Fortluftklappe manuelle Bedienung?ffnungsz0/1rw1,(2),5x 1080010800Cond.fan1configuration active Kond.-Ventilator1Konfiguration aktiv0/1r1,(2)x CC2 1080110801Cond.fan1manual operation active Kond.-Ventilator1manuelle Bedienung aktiv0/1rw1,(2),5x CC2 1080210802Cond.fan1running Kond.-Ventilator1l?uft0/1r2,(1)x CC2 1080310803Cond.fan1alarm active Kond.-Ventilator1Alarm aktiv0/1r2,(1)x CC2 1080410804Cond.fan1common alarm configured Kond.-Ventilator1gemeinsamer Alarm konfig0/1r1,(2)x CC2 1090010900Cond.fan2configuration active Kond.-Ventilator2Konfiguration aktiv0/1r1,(2)x CC2 1090110901Cond.fan2manual operation active Kond.-Ventilator2manuelle Bedienung aktiv0/1rw1,(2),5x CC2 1090210902Cond.fan2running Kond.-Ventilator2l?uft0/1r2,(1)x CC2 1090310903Cond.fan2alarm active Kond.-Ventilator2Alarm aktiv0/1r2,(1)x CC2 1090410904Cond.fan2common alarm configured Kond.-Ventilator2gemeinsamer Alarm konfig0/1r1,(2)x CC2 1100011000Filter1configuration active Filter1Konfiguration aktiv0/1r1,(2)x 1100111001Filter1alarm active Filter1Alarm aktiv0/1r2,(1)x 1100211002Filter1common alarm configured Filter1gemeinsamer Alarm konfiguriert0/1r1,(2)x 1100311003Filter1action on alarm Filter1Wirkung auf Alarm0/1rw1,(2)x 1110011100Filter2configuration active Filter2Konfiguration aktiv0/1r1,(2)x 1110111101Filter2alarm active Filter2Alarm aktiv0/1r2,(1)x 1110211102Filter2common alarm configured Filter2gemeinsamer Alarm konfiguriert0/1r1,(2)x 1110311103Filter2action on alarm Filter2Wirkung auf Alarm0/1rw1,(2)x 1120011200Filter3configuration active Filter3Konfiguration aktiv0/1r1,(2)x 1120111201Filter3alarm active Filter3Alarm aktiv0/1r2,(1)x 1120211202Filter3common alarm configured Filter3gemeinsamer Alarm konfiguriert0/1r1,(2)x 1120311203Filter3action on alarm Filter3Wirkung auf Alarm0/1rw1,(2)x 1130011300External Filter configuration active Externer Filter Konfiguration aktiv0/1r1,(2)x 1130111301External Filter alarm active Externer Filter Alarm aktiv0/1r2,(1)x 1130211302External Filter common alarm configured Externer Filter gemeinsamer Alarm konfigurie0/1r1,(2)x 1130311303External Filter action on alarm Externer Filter Wirkung auf Alarm0/1rw1,(2)x 1140011400GE/CW-valve1config active0/1r1,(2)x 1140111401GE/CW-valve1manual operation active0/1rw1,(2),5x 1140311403GE/CW-valve1close if WT over SP0/1r1,(2)x 1140411404GE/CW-valve1heating permitted0/1r1,(2)x 1140511405GE/CW-valve1analog output inverted0/1r1,(2)x 1145011450GE/CW-valve2config active0/1r1,(2)x 1145111451GE/CW-valve2manual operation active0/1rw1,(2),5x 1145311453GE/CW-valve2close if WT over SP0/1r1,(2)x 1145411454GE/CW-valve2heating permitted0/1r1,(2)x 1145511455GE/CW-valve2analog output inverted0/1r1,(2)x 1150011500ICC configured IKK konfiguriert0/1rw1,(2)x 1150111501manual operation manuelle Bedienung0/1rw1,(2)x 1150211502common alarm availability gemeinsamer Alarm Verfügbarkeit0/1rw1,(2)x 1150311503common alarm upc gemeinsamer Alarm upc0/1rw1,(2)x 1150411504common alarm low pressure gemeinsamer Alarm niederdruck0/1rw1,(2)

1150511505compressor power on,uPC DP42Kompressor l?uft,uPC DP420/1r1,(2)x 1150611506enable to operate,uPC DP46Betrieb erm?glicht,uPC DP460/1r1,(2)x 1170811708my zone CW energy save mode activ meine Zone CW Energiesparmodus aktiv0/1r1,(2)x 1170911709my zone testsequencing meine Zone Testsequenzierung0/1r1,(2)x x

Stulz-Adr.MODBUS-

adr.Description Beschreibung Modbus range mapped meaning

BMS-

access

Modbus-

function C7000IOC

C7000IOC

Chiller

1171011710my zone average determination of temp.and m eine Zone Durchschnittsbestimmung von Te0/1r1,(2)x x 1171311713my zone average determination of air pressur meine Zone Durchschnittsbestimmung vom L0/1r1,(2)x 1171411714my zone average determination of room press

meine Zone Mittelwertbildung Raumdruck0/1r1,(2)x 1180011800emergency operation active Notbedienung aktiv0/1r2,(1)

1420114201max.delta p exceeded max.Delta püberschritten0/1ok/alarm r2,(1)x 1420314203compressor cabinet temp too high Kompressorraumtemp zu hoch0/1ok/alarm r1,2CC2 1420414204electric cabinet temp too high Schaltschranktemp zu hoch0/1ok/alarm r1,2CC2 1420514205protection device compressor1Schutzgeraet,Kompr.10/1ok/alarm r1,2CC2 1420614206protection device compressor2Schutzgeraet,Kompr.20/1ok/alarm r1,2CC2 1420714207protection device compressor3Schutzgeraet,Kompr.30/1ok/alarm r1,2CC2 1420814208protection device compressor4Schutzgeraet,Kompr.40/1ok/alarm r1,2CC2 1420914209protection device compressor5Schutzgeraet,Kompr.50/1ok/alarm r1,2CC2 1421014210protection device compressor6Schutzgeraet,Kompr.60/1ok/alarm r1,2CC2 1421114211alarm state that shut off compressor envelop A larmzustand der den Kompressor ausgesch0/1ok/alarm r1,2x 1421214212bms offline heart bit fails,uPC DP40GLT nicht erreichbar,uPC DP400/1ok/alarm r1,2x 1421314213global general alarm,uPC DP45globaler allgemeiner Alarm,uPC DP450/1ok/alarm r1,2x 1421414214delta p larger allowable start up,uPC DP47Druckdifferenz gr??er als zum starten des uP0/1ok/alarm r1,2x 1421514215dp start disable alarm,uPC DP49DD Startverhinderungsalarm,uPC DP490/1ok/alarm r1,2x 1421614216min.oil level comp.1min.Oelstand Komp.10/1ok/alarm r1,2CC2 1421714217min.oil level comp.2min.Oelstand Komp.20/1ok/alarm r1,2CC2 1421814218min.oil level comp.3min.Oelstand Komp.30/1ok/alarm r1,2CC2 1421914219min.oil level comp.4min.Oelstand Komp.40/1ok/alarm r1,2CC2 1422014220min.oil level comp.5min.Oelstand Komp.50/1ok/alarm r1,2CC2 1422114221min.oil level comp.6min.Oelstand Komp.60/1ok/alarm r1,2CC2 1422214222power switch comp.1Leistungschalter Komp.10/1ok/alarm r1,2CC2 1422314223power switch comp.2Leistungschalter Komp.20/1ok/alarm r1,2CC2 1422414224power switch comp.3Leistungschalter Komp.30/1ok/alarm r1,2CC2 1422514225power switch comp.4Leistungschalter Komp.40/1ok/alarm r1,2CC2 1422614226power switch comp.5Leistungschalter Komp.50/1ok/alarm r1,2CC2 1422714227power switch comp.6Leistungschalter Komp.60/1ok/alarm r1,2CC2 1422814228envelope left comp.1Grenzverletzung Komp.10/1ok/alarm r1,2CC2 1422914229envelope left comp.2Grenzverletzung Komp.20/1ok/alarm r1,2CC2 1423014230envelope left comp.3Grenzverletzung Komp.30/1ok/alarm r1,2CC2 1423114231envelope left comp.4Grenzverletzung Komp.40/1ok/alarm r1,2CC2 1423214232envelope left comp.5Grenzverletzung Komp.50/1ok/alarm r1,2CC2 1423314233envelope left comp.6Grenzverletzung Komp.60/1ok/alarm r1,2CC2 1423414234freecool failed(intermediate temp.high)FK misslungen(Zwischentemp.Erhoeht)0/1ok/alarm r1,2CC2 10162032unit year Einheit Jahr0..992000..2099r3,(4)x x 10172034unit month Einheit Monat 1..12 1..12r3,(4)x x 10182036unit day Einheit Tag 1..31 1..31r3,(4)x x 10192038unit hour Einheit Stunde0..230..23r3,(4)x x 10202040unit minute Einheit Minute0..590..59r3,(4)x x 10212042unit second Einheit Sekunde0..590..59r3,(4)x x 10302060IOC service language IOC Sprach-Service0..10=English;1=German r3,(4)x x 11602320unit last maintenance year Einheit letzte Wartung,Jahr0..992000..2099r3,(4)x x 11612322unit last maintenance month Einheit letzte Wartung,Monat 1..12 1..12r3,(4)x x

通信电源规约CSU03B通信协议-通信局电源、空调及环境集中监控管理系统前端智能设备通信协议

CSU03B通信协议更改记录 2006-06-13:V1.0;其中历史告警记录有重大调整,其他与CSU03A兼容。

CSU03B通信协议 本协议以电信总局《通信局(站)电源、空调及环境集中监控管理系统前端智能设备通信协议》(一九九九年三月)为基础制定;与CSU03A通信协议兼容(历史数据和历史告警除外)。 一.物理接口 1.串行通信口采用RS232/RS485,数据传输速率2400bps; 2.信息传输方式为异步方式,起始位1位,数据位8位,停止位1位,无校验。 3.局站监控系统(SU)与设备监控单元(SM)的通信为主从方式。SU呼叫SM并下发命令,SM收到命令后返回响应信息。SU500ms内收不到SM响应或接收响应信息错误,则认为本次通信过程失败。 二.信息类型及协议的基本格式 1.信息分两种类型: (1) 由SU发出到SM的命令信息(简称命令信息); (2) 由SM返回到SU的响应信息(简称响应信息)。 基本格式的注解见表2.2、表2.3。 表2.2 协议的基本格式 说明: COMMAND INFO由以下控制命令码(其中一部分)组成: COMMAND GROUP(1字节):表示同一类型设备的不同组号; COMMAND ID(1字节):表示同一类型设备相同组内的不同监控点; COMMAND TYPE(1字节):表示不同的遥控命令或历史数据传输中的不同控制命令; COMMAND TIME(1字节):表示时间字段。 DA TA INFO由以下应答码(其中一部分)组成: DATAI:含有整型数的应答信息;

RUNSTATE:设备的运行状态; WARNSTA TE:设备的告警状态; DATAFLAG:标示字节;本协议中该字节无效,固定为00H; DATATIME:时间字段。 表2.3返回码RTN 3.数据格式 3.1 基本数据格式 在表2.1基本格式中各项除SOI和EOI是以十六进制解释(SOI=7EH,EOI=0DH),十六进制传输外,其它各项都是十六进制解释,十六进制—ASCII码的方式传输,每个字节用两个ASCII码表示,即高四位一个ASCII码表示,低四位用一个ASCII码表示。 例:CID2=4BH,传送时顺序发送34H和42H两个字节。 3.2 LENGTH数据格式 LENGTH共两个字节,由LENID和LCHKSUM组成,LENID表示INFO项的ASCII 码字节数,当LENID=0时,INFO为空,即无该项。LENGTH传输中先传高字节,再传低字节,分四个ASCII码传送。 校检码的计算:D11D10D9D8+D7DD6D5D4+D3D2D1D0,求和后模16余数取反加1。例:I NFO项的ASCII码字节数为18,即LENID=0000 0001 0010B。 D11D10D9D8+D7D6D5D4+D3D2D1D0=0000B+0001B+0010B=0011B,模16余数为0011B,0011B取反加1就是1101B,即LCHKSUM为1101B。 可得: LENGTH为1101 0000 0001 0010B,即D012H。 3.3 CHKSUM数据格式 CHKSUM的计算是除SOI、EOI和CHKSUM外,其他字符按ASCII码值累加求和,所得结果模65536余数取反加1。 例:收到或发送的字符序列是:“~1203400456ABCDFEFC72C C R R”(“~”为SOI,“C C R R”为EOI),则最后五个字符“FC72C C R R”中的FC72是CHKSUM,计算方法是: ‘1’+‘2’+‘0’+…+‘A’+‘B’+…+‘F’+‘E’ = 31H + 32H + 30H + …+ 41H + 42H + …+ 46H + 45H = 038EH 其中‘1’表示1的ASCII码值,‘E’表示E的ASCII码值。038EH模65536余数是

格力GMV多联机系列常见机型介绍

格力中央空调多联机介绍 本文对市面上常见的格力多联机机型做了一些介绍。详情可见公司官网: 1、Free系列直流变频多联机组 Free系列直流变频多联空调机组,是格力公司自主研制开发的新型多联空调机组,结合中央空调的舒适、高档和分体空调机安装方便、灵活等优势,运行经济高效。 Free系列直流变频多联空调机组可广泛适用于中小型超市、连锁店、宾馆、酒楼、餐厅、办公室、会议室等。 ★单室外机:只有一个室外机,安装省时、省工、省空间,安全可靠、美观大方。 ★多室内机:室内机有风管送风式和挂壁式两大类,可根据实际需要任意选配;一个室外机带多个室内机可同时满足单个或多个房间使用,每个室内机可单独控制,使用方便。 ★多种余压设计,使用范围广:同一风管送风式室内机只需改变室内机接线就可进行高静压或普通静压运行,使用方便、范围广。 ★内机安装灵活:根据实际情况,室内机可以灵活确定送回风形式、冷凝水接出方向、风口型式。 ★更精心设计:机组结构设计科学,安装、检测、维修、保养极为方便;室内机身高度最薄185mm,最高仅300mm。 ★保温材料性能优良:室内机采用优质保温材料,防潮、不腐烂、不滋生细菌、不产生化学气体、不掉下碎屑、同时具有高热阻、隔噪音、避震动等性能。 ★运行可靠:机组安全保护功能齐全,具有强大故障自诊断功能;(详见“微电脑控制系统”)。 ★高效节能:采用名牌压缩机;蒸发器采用亲水膜铝箔、内螺纹铜管,换热效率高,提高了机组的能效比。 ★室内空气品质好:机组送风管可接多个风口,使室内空调温湿度达到均匀,并且风管送风式室内机预留的新风管可接入新风,室内空气质量优良。 ★使用方便:简洁的全中文控制器(或灵活的遥控器)使你对机组控制自如。 适用场所:Free系列直流变频多联空调机组可广泛适用于中小型超市、连锁店、宾馆、酒楼、餐厅、办公室、会议室等。特别适合中小型商用和工业应用建筑空调工程。 2、GH系列家用一拖多空调机组 GH系列家用一拖多空调机组使用特性 1、所有房间一个空调系统,整体运行更加节能; 2、内机可引入新风,提高室内空气品质;

施耐德空调UG40通讯协议

UG40----NEW LEONARDO: DIGITAL VARIABLES (COILS) variable address description variable type MODBUS Database (e.g. address -> bit nr.) unit 1 unit 2 unit 3 unit n 0 Not used … 1 201 401 (n-1)*200+1 1 System On (Fan) R 2 202 402 (n-1)*200+2 2 Compressor 1 R 3 203 403 (n-1)*200+3 3 Compressor 2 R 4 204 404 (n-1)*200+4 4 Compressor 3 R 5 205 405 (n-1)*200+5 5 Compressor 4 R 6 206 406 (n-1)*200+6 6 El. Heater 1 R 7 207 407 (n-1)*200+7 7 El. Heater 2 R8 208 408 (n-1)*200+8 8 Not Used R9 209 409 (n-1)*200+9 9 Hot gas ON R10 210 410 (n-1)*200+10 10 Dehumidification R11 211 411 (n-1)*200+11 11 Humidification R12 212 412 (n-1)*200+12 12 Emergency Working R13 213 413 (n-1)*200+13 13 Not used…14 214 414 (n-1)*200+14 14 Not used…15 215 415 (n-1)*200+15 15 Not used…16 216 416 (n-1)*200+16 16 Not used…17 217 417 (n-1)*200+17 17 Not used…18 218 418 (n-1)*200+18 18 Not used…19 219 419 (n-1)*200+19 19 Not used…20 220 420 (n-1)*200+20 20 Wrong Password Alarm R21 221 421 (n-1)*200+21 21 High Room Temperature Alarm R22 222 422 (n-1)*200+22 22 Low Room Temperature Alarm R23 223 423 (n-1)*200+23 23 High Room Humidity Alarm R24 224 424 (n-1)*200+24 24 Low Room Humidity Alarm R25 225 425 (n-1)*200+25 25 Room Temp. And Humidity Limits by External Sensors R26 226 426 (n-1)*200+26 26 Clogged Filter Alarm R27 227 427 (n-1)*200+27 27 Flooding Alarm R28 228 428 (n-1)*200+28 28 Loss of Air Flow Alarm R29 229 429 (n-1)*200+29 29 Heater Overheating Alarm R30 230 430 (n-1)*200+30 30 Circuit 1 High Pressure Alarm R31 231 431 (n-1)*200+31 31 Circuit 2 High Pressure Alarm R32 232 432 (n-1)*200+32 32 Circuit 1 Low Pressure Alarm R33 233 433 (n-1)*200+33 33 Circuit 2 Low Pressure Alarm R34 234 434 (n-1)*200+34 34 Circuit 1 Electronic Valve Failure R35 235 435 (n-1)*200+35 35 Circuit 2 Electronic Valve Failure R36 236 436 (n-1)*200+36 36 Wrong Phase Sequence Alarm R37 237 437 (n-1)*200+37 37 Smoke-Fire Alarm R38 238 438 (n-1)*200+38 38 Interrupted LAN Alarm R39 239 439 (n-1)*200+39 39 Humidifier: High Current Alarm R40 240 440 (n-1)*200+40 40 Humidifier: Power Loss Alarm R41 241 441 (n-1)*200+41

空调参数及其型号

空调参数及其型号 商场里空调的价签上除了价格以外,往往还有一串数字和字母表示空调的型号。别小看这些数字和字母,某款空调是第几代产品,都有哪些功能,行家一眼就能看出来。下面我就给您说说这些数字和字母的含义。 空调型号的表示方法国家有统一的标准,基本格式为“①②③—④⑤⑥⑦⑧”。 处于①位置上的字母表示产品代号,如果为K,则表示是家用空调器。 处于②位置上的字母表示空调的结构形式,空调器按结构形式分为整体式和分体式,整体式空调器又分为窗式和移动式,代号分别为:F为分体式,C为窗式,Y为移动式。 ③表示功能代号(单冷型无此代号)。R为热泵型,Rd为热泵辅助电加热,D为电热型。 ④表示额定制冷量,用阿拉伯数字表示。 ⑤表示分体式室内机组结构代号,D为吊顶式、G为挂壁式、L为落地式、Q为嵌入式等。 ⑥表示分体式空调器室外机代号,W代表室外机。 ⑦表示改进型代号。分为A、B、C、D、E等,在字母前面加斜杠以区分。 ⑧表示工厂设计序号和特殊功能代号等,允许用汉语拼音大写字母或阿拉伯数字表示,如变频为BP,遥控为Y。 下面以格力空调几个型号作简单说明: KCD-46(4620):其中K表示房间空调器,C表示窗机,D表示电热型,46表示制冷量是4600瓦。 KFR-25GWE(2551):其中K表示房间空调器,F表示分体式,R表示热泵型,25表

示制冷量是2500瓦,G表示挂壁式,W表示室外机代号,E表示该型号为改进型产品,即冷静王系列产品。(晋平) 格力空调机型号中的N4、N5是表示能效比。能效比:N5-2.6以上,N4-2.8以上,N3-3.0以上,N2-3.2以上,N1-3.4以上,N后数字越小能效比越高,越省电。国家规定9月1日起能效比2.6以下的空调不能进入市场。格力为了方便区分,设了一个能源级别来明确标明,实际没标明的也和标明的是一样的机器,只是差了一个标识。 所谓能效比也称性能系数,即一台空调器的名义制冷量与其耗电功率的比值。通常,空调器的能效比接近3或大于3为佳,就属于节能型空调器。比如,一台空调器的制冷量是2000W,额定耗电功率为640W,另一台空调器的制冷量为2500W,额定耗电功率为9 70W。则两台空调器的能效比值分别为:第一台空调器的能效比:2000W/640W=3.125,第二台空调器的能效比:2500W/970W=2.58。 附:国家新颁布的空调能效标准共分五级,能耗比是制冷量除以输出功率的比值,最低标准是一级2.6,按照新规定,能耗比低于2.6即为不合格产品。估计现在市场上还有3 0%的库存量达不到国家标准,所以厂商也在积极清库存。 级别能耗比级别能耗比 五 3.4二 2.8 四 3.2一 2.6 三 3.0 KFR-32GW和KFR-32GE4区别:前者是挂壁式的室外机,后者为挂壁式的改进E型;能效比为4级。 KFR-72LW与KFR-72GD5的区别:前者为落地式室外机,后者为挂壁式改进D型,能效比为5级。 二, KFRd-50LW/U(ZXF)

Joton空调通讯协议(恒温恒湿普通系列)

机房专用空调Tmaster通讯协议 1物理接口 1.1 串行通信口可采用RS485。 1.2 信息传输方式为异步方式,起始位1位,数据位8位,停止位1位,无校验。 1.3 采用RS485通信口时,数据传输速率为可选(出厂设置为9600)。 2.信息类型及协议的基本格式 2.1 信息类型 信息分两种类型: (1) 由SU发出到SM的命令信息(简称命令信息); (2) 由SM返回到SU的响应信息(简称响应信息)。 2.2 协议的基本格式 序号 1 2 3 4 5 6 7 8 9 字节数 1 1 1 1 1 2 LENID/2 2 1 格式 SOI VER ADR CID1 CID2 LENGTH INFO CHKSUM EOI 基本格式的注解见表2.2.1、表2.2.2。 表2.2.1 序号符号表示意义备注 1 SOI 起始位标志(START OF INFORMATION)(7EH) 2 VER 通信协议版本号 2.0 (20H) 3 ADR 设备地址描述(1-32) 4 CID1 控制标识码(设备类型描述)(60H) 5 CID2 命令信息:控制标识码(数据或动作类型描述) 响应信息:返回码RTN(见返回码表2.2.2) 6 LENGTH INFO字节长度(包括LENID和LCHKSUM),数据格式 见7.3 7 INFO 命令信息:控制数据信息COMMAND INFO 应答信息:应答数据信息DATA INFO 8 CHKSUM 校验和码,数据格式见2.3 9 EOI 结束码CR (0DH) 说明: COMMAND INFO由以下控制命令码组成: COMMAND GROUP(1字节):表示同一类型设备的不同组号; COMMAND ID(1字节):表示同一类型设备相同组内的不同监控点; COMMAND TYPE(1字节):表示不同的遥控命令中的不同控制命令; COMMAND TIME(1字节):表示时间字段。 DATA INFO由以下应答码组成: DATAI:含有整型数的应答信息; DATAF:含有浮点数的应答信息; RUNSTATE:设备的运行状态; WARNSTATE:设备的告警状态;

空调一拖三的通信协议

产品型号、名称直流一拖三 三、附录: 模拟外机板与内机板通讯协议 1.变频一拖多空调室内外机通讯采用国际标准的串行异步通讯方式进行数据通讯 2.通讯开始时,以外机主。外机上电复位后,延时5S之后开始通讯,向A机发送通讯数 据;发送完毕后立即转入接收状态(10ms内),如正常接收到A机发回的通讯数据,并检验正确,则直接转到向B机发送通讯数据,如等2S后为收到A机发回的通讯数据,则直接转到向B机发送通讯数据。以此类推,当接收完最后一个标号内机通讯数据后,或等足够时间2秒钟之后,重新回到A机通讯。 3.内机通讯处理:所有内机上电复位完成后,进入通讯接收等待状态。当内机接收完室外 机通讯数据并检验正确后,必须立即转入发送状态,延时20MS之后开始发送数据,但最迟必须在50ms之内开始向室外机发送通讯数据。 4.室内机连续4分钟之内无法收到室外机通讯信号,确认通讯故障,室外机不处理通讯故 障。 5.数据格式定义为1位起始位、8位数据位1奇校验位、1位停止位;波特率为600。每 ↓共发送25个字节。 6.用户引导码:E7H, 18H, AAH, 55H 。(室内机与室外机相同 7.内机发往模拟外机的数据内容: 第00字节:固定为01 。(源地址) 第01字节:固定为FFH(目标地址) 第02字节:固定为01H。(数据类型) 第03字节: 第03字节: B0: 开关机:0为关机。1为开机 B2,B1: 功能模式: 00为制冷,01为制热;10除湿。 B3: 0为无安静, 1为安静运行 B4:额定功率运行:0为通常 1为额定 B5:0为除湿低频运行 1为除湿高频运行 B6: 0为无强力运行 1为强力运行 B7: 一直发1强制频率运行 (备注:B3~B7最多同时只有一位为“1”。) 第04字节: B0: 0为通常 1为最大强力运行 B1: 0为通常 1为半能力运行 B2 0为通常 1为最小能力运行 B3: 0为通常 1为低温制热运行

空调型号的含义

1、家用房间空调器用字母 K 表示,即空调型号中 KFR-23GW/HA 2、空调器按结构形式分为整体式和分体式,整体式空调器又分为窗式和移动式,代号分别为:分体式—F 、窗式—C 、移动式—Y ,即空调型号中 KFR-23GW/HA 3、空调器按功能主要分为单冷型、热泵型及电热型,单冷型代号省略,热泵型、 电热型代号分别 R 、D ,即空调型号中 KFRD-23GW/HA 。 4、室内机组结构分类为吊顶式、挂壁式、落地式、天井式、嵌入式等,其代号分别为D、G 、 L、T 、Q等,即空调型号中 KFR-23GW/HA, 代表挂壁式,其余类型以此类推 5、室外机组代号为 W ,即空调型号中 KFR-23GW/HA 。G3]R;G 6、匹的含义:习惯性对空调的称谓是1匹,1.5匹,2匹,3匹,5匹等,匹即马力是功率的换算单位.1匹=735瓦,指压缩机耗电量,加上内外风机,控制电路等,1匹空调总耗电量约850瓦左右(不含电辅助加热功耗),依此类推2匹空调耗电量约1600瓦左右(带电辅助加热器的应在2600-3000瓦) 7、KFR-23GW中的23是指空调的制冷量,为23X100即2300瓦。KFR-50LW即分体立柜式冷暖空调,制冷量为5000瓦,耗电量约为1600W。 空调基本适用面积 1、1匹空调(KFR-23-26GW)适合 12-16 平方米左右的空间。 2、1.5匹空调(KFR-32-35GW)适合 18-25平方米左右的空间。 3、2匹空调(KFR-45-50LW)适合 28-40平方米左右的空间。 4、2.5匹空调(KFR-60LW)适合 40-50 平方米左右的空间。 5、3匹空调(KFR-70LW)适合 50-70平方米左右的空间。 6、5匹空调(KFR-120LW)适合 70-100 平方米左右的空间。 空调制冷原理bYD 空调器通电后,制冷系统内制冷剂的低压蒸汽被压缩机吸入并压缩为高压蒸汽后排至冷凝器。同时轴流风扇吸入的室外空气流经冷凝器,带走制冷剂放出的热量,使高压制冷剂蒸汽凝结为高压液体。高压液体经过过滤器、毛细管节流后喷入蒸

艾默生空调ACM03U1制器监控通讯协议1.00

协议图号05125398-XY 版本V100 第1页共22 页 ACM03U1控制器监控 通讯协议 艾默生网络能源有限公司

目次 1.物理接口 (3) 2.通信方式 (3) 3.信息类型及协议的基本格式 (3) 3.1信息类型 (3) 3.2协议的基本格式 (3) 3.3数据格式 (5) 3.3.1 基本数据格式 (5) 3.3.2 LENGTH数据格式 (5) 3.3.3 CHKSUM数据格式 (6) 3.3.4 INFO数据格式 (6) 4.编码表 (6) 5.协议内容 (7) 5.1获取模拟量数据(定点数)(42H) (7) 5.2获取开关输入状态(43H) (8) 5.3遥控开关机(45H) (10) 5.4获取系统参数(定点数)(47H) (10) 5.5设定系统参数(定点数)(49H) (11) 5.6获取监测模块时间(4DH) (12) 5.7设定监测模块时间(4EH) (13) 5.8获取通信协议版本(4FH) (13) 5.9获取设备地址(50H) (14) 5.10获取厂家信息(51H) (15) 5.11获取机组状态(82H) (15) 5.12获取机组运行模式和报警状态(85H) (17) 5.13获取模拟量输出(86H) (21)

精密空调控制器监控协议 本文规定了精密空调控制器与后台监控、之间的通讯协议规范。本文以电总协议:《监控行标第三部分:智能设备通信协议》为依据,根据精密空调规范而制定,并扩展了相应命令。 1.物理接口 串行通信口采用RS485/RS232。 信息传输方式为异步方式,起始位1位,数据位8位,停止位1位,无校验。 数据传输速率为1200、2400、4800、9600和19200bits可以设置。 2.通信方式 在局站内的监控系统为分布式结构。局站监控单元(SU)与设备监控模块(SM)的通信为主从方式,监控单元为上位机,监控模块为下位机。SU呼叫SM并下发命令,SM 收到命令后返回响应信息。SU 500ms内接收不到SM响应或接收响应信息错误,则认为本次通信过程失败。 在本系统中,精密空调控制器为SM,上位机为SU 3.信息类型及协议的基本格式 3.1信息类型 信息分两种类型: (1) 由SU(上位机)发出到SM(精密空调控制器)的命令信息(简称命令信息); (2)由SM(精密空调控制器)返回到SU(上位机)的响应信息(简称响应信息)。 3.2协议的基本格式 注意:在基本格式中的各项除SOI和EOI是以十六进制解释(SOI = 7EH,EOI = 0DH),

空调型号的含义

空调型号的含义 对于空调命名来说,我们用一个产品为例为大家做简单介绍,我们以具体型号为KFR-50LW/BP3DN1Y-C的空调为例。下面我们就简要为大家介绍一些这款立柜空调的命名方法,也希望以此为基础,让各位了解更多的空调命名规则。 KFR-50LW/BP3DN1Y-C K:空调或表示房间空调器 F:分体式 R:冷暖型,单冷型无此标识 50:制冷量为5000瓦 L:立式柜机(G:壁挂型空调) W:外机 BP:变频式 3:三级能效 D:电辅热功能 N1:R410A环保冷媒 Y:遥控控制 C:型号区别码,即此机为变频系列里C款机型。 一、空调的主要参数 制冷量和制热量:空调调节室内气温的能量。例如50机的制冷量5000W,制热量5800W。 二、制冷功率和制热功率:空调的耗电量。例如50机的制冷功率1860W,制热 功率1810W + 辅助电加热功率1500W=3310 W。 三、能效比:空调制冷量与制冷功率的比值。例如50机的能效比是5000÷1860 =2.69 四、卖场所称空调的“匹”数,例如“1匹”、“1.5匹”、“2匹”等等,是一种约定俗成 的说法,指空调的制冷量。 五、空调主要机型的型号标识及其含义: 1. KFR-25GW,简称25机; 2. KFR-35GW,简称35机; 3. KFR-50LW,简称50机; 4. KFR-60LW,简称60机; 5. KFR-70LW,简称70机; 6. KFR-120LW,简称120机。 六、25、35、50、60、70、120:表示制冷量。分别为2500瓦、3500瓦、5000 瓦、6000瓦、7000瓦、12000瓦。其他数值的制冷量以此类推。空调型号字母中有“R”的为冷暖空调;没有“R”的是单冷空调。在上述型号字母之后标有“BP”的,表示变频空调;没有“BP”的,表示定速空调;标有“ZBP”的,表示直流变频空调。其他的字母数字是空调的系列号。三、空调主要机型对应的匹数: 1. 25机:1匹; 2. 35机:1.5匹; 3. 50机:2匹; 4. 60机:2.5匹; 5. 70机:3匹; 6. 120机:5匹。 七、卖场习惯将以上6种标称,称为“正* 匹”;大于以上标称的称为“大* 匹”;小于以上标称的称为“小* 匹”。

空调C7000通讯协议(世图兹 ASD531a)

Stulz-Adr. MODBUS- adr.Description Beschreibung Modbus range mapped meaning BMS- access Modbus- function C7000IOC C7000IOC Chiller 00hardware type(controller type)Hardware-Typ(Steuerungs-Typ)0..13=C7000IOC;8=C7000AT;9=C700r3,(4)x x 88general error Allgemeiner Fehler0/1ok/error r1,(2)x x 12unit-type unit-type0..2551=CHP;12=FAU;13=CPP;14=Pr r3,(4)x x 36SW-version SW-Version0..655,35Version0..655,35Version r3,(4)x x 510Bus-ID Bus-ID0..310..31r3,(4)x x 612global adress Globale Adresse0..65535r3,(4)x x

Stulz-Adr. MODBUS- adr.Description Beschreibung Modbus range mapped meaning BMS- access Modbus- function C7000IOC C7000IOC Chiller 0 see combined list C7000common s.gemeinsame Liste C7000common 999 10001000PC-STOP(monitoring),BMS stop1PC-STOP(überwachung),BMS stop10/1maybe on/unit off rw1,(2),5x x 10011001REMOTE STOP(contact)FERN-STOP(Kontakt)0/1maybe on/unit off r1,(2)x x 10021002LOCAL STOP LOKAL-STOP0/1maybe on/unit off r1,(2)x x 10031003TIMER-STOP(weekly oper.)TIMER-STOP(w?chentlicher Betrieb)0/1maybe on/unit off r1,(2)x x 10041004SEQ.Stop(0=No,1=Yes)SEQ.Stop(0=Nein,1=Ja)0/1maybe on/unit off r1,(2)x x 10051005WARM UP STOP AUFW?RMEN STOP0/1maybe on/unit off r1,(2)x x 10061006Remote UPS FERN-UPS0/1inactive/active rw1,(2),5x x 10071007Local UPS Lokal-UPS0/1inactive/active r2,(1)x x 10081008G/CW-mode;G:1,CW:0G/CW-Modus;G:1,CW:00/1CW/G r1,(2)x 10091009manual operation manueller Betrieb0reset man.op./rw1,(2),5x x 10101010common alarm gemeinsamer Alarm0/1no alarm/alarm r2,(1)x x 10111011reset all alarms Alle Alarme zurückstellen0/1/reset rw1,(2),5x x 10121012manual operation raw output manueller Betrieb Roh-Output0/1inactive/active r1,(2)x x 10131013Unit on/off Einheit on/off0/1off/on r2,(1)x x 10141014maintenance necessary Wartung notwendig0/1no/yes r2,(1)x x 10221022unit temperature phys.unit Einheit Temperatur phys.Einheit0/1Celsius/Fahrenheit r1,(2)x x 10231023unit winter mode Einheit Winter-Modus0/1Summer/Winter r2,(1)x x 10241024day/night-mode Tag/Nacht-Modus0/1day/night r2,(1)x x 10251025CW2change-over CW2Umstellung0/1/force change over rw2,(1)x x 10261026CW2change-over state CW2Umstellungs-Status0/1/change over done r2,(1)x 10281028unit start by remote-on/off Start der Einheitüber Fernsteuerung on/off0/1inactive/active r2,(1)x x 10321032unit firmware-option1:OTE(automatic alarm Einheit firmware-Option1:OTE(automatische0/1r2,(1)x x 10331033unit firmware-option2:restart after fire alarm Einheit firmware-Option2:Neustart nach erle0/1r2,(1)x x 10341034unit firmware-option3:auto alarm reset for lim Einheit firmware-Option3:Alarm-Selbstrücks0/1r2,(1)x x 10351035unit firmware-option4:special control of fans E inheit firmware-Option4:Spezialkontrolle vo0/1r2,(1)x x 10361036unit firmware-option5:special control of pump Einheit firmware-Option5:Spezialkontrolle Pu0/1r2,(1)x x 10371037unit firmware-option6:special control Adaptiv Einheit firmware-Option6:Spezialkontrolle Ad0/1r2,(1)x x 14921492water inlet1,min temperature commonalarm Wassereinlass1,Min.-Temperatur gemeinsa0/1r1,(2)x 14931493water inlet1,max temperature commonalarm W assereinlass1,Max.-Temperatur gemeinsa0/1r1,(2)x 14941494water outlet1,min temperature commonalarm Wasserauslass1,Min.-Temperatur gemeinsa0/1r1,(2)x 14951495water outlet1,max temperature commonalarm Wasserauslass1,Max.-Temperatur gemeins0/1r1,(2)x 14961496water inlet2,min temperature commonalarm Wassereinlass2,Min.-Temperatur gemeinsa0/1r1,(2)x 14971497water inlet2,max temperature commonalarm W assereinlass2,Max.-Temperatur gemeinsa0/1r1,(2)x 14981498water outlet2,min temperature commonalarm Wasserauslass2,Min.-Temperatur gemeinsa0/1r1,(2)x 14991499water outlet2,max temperature commonalarm Wasserauslass2,Max.-Temperatur gemeins0/1r1,(2)x 15001500circuit1LP management common alarm conf LP Management gemeinsamer Alarm Konfigu0/1r1,(2)x x 15301530circuit1HP management common alarm con HP Management gemeinsamer Alarm konfig0/1r1,(2)x x 16001600circuit2LP management common alarm conf LP Management gemeinsamer Alarm Konfigu0/1r1,(2)x CC2 16301630circuit2HP management common alarm con HP Management gemeinsamer Alarm konfig0/1r1,(2)x CC2 17421742fire alarm common alarm config Feueralarm gemeinsamer Alarm konfig0/1r1,(2)x x 17431743water alarm common alarm config Wasseralarm gemeinsamer Alarm konfig0/1r1,(2)x x 17441744phase alarm common alarm config Phase Alarm gemeinsamer Alarm konfig0/1r1,(2)x x

格力空调厂方提供远程通讯协议

格力吸顶空调应具备远程控制功能,由格力空调厂方提供远程通讯协议: 空调应具有以下功能: 1、能通过RS232/RS485方便地与计算机进行通信。 2、远程提供空调机的运行参数、运行状态,包括当前的温度、湿度、设备所处的工作状态等,并对空调机的某些参数进行远程设置。 3、提供空调机的系统设置参数,包括:温度设定、湿度设定、高温告警、低温告警等。 4、远程读取空调的运行状态,包括工作方式、风扇转速等;远程读取空调告警信息。 5、工作人员可通过计算机遥控。 附件: 远程监控和电话遥控通讯协议 版本:V1.0 通讯内容 一、数据传输率:4800BPS,8位数据位,1位停止位,偶校验 二、从空调控制器获取工作参数及返回空调控制器工作参数(空调控制器机号在此不做判断):

一.)当空调控制器接收到如下数据时,表明从空调控制器获取工作参数而空调控制器不接收:(与上位机无关) 1、起始码(1 byte)(06H) 2、下位机固定地址(4bytes) (30H 30H 30H 30H) 3、遥控编码(8 bytes) (ASC码) 4、校验码 (2 bytes) (ASC码) 5、结束码(1 byte) (0DH) 二.)空调控制器返回工作参数:见四、此时不判断机号 三、空调控制器按传来的工作参数执行: 一.)当空调控制器接收到如下数据时,表明空调控制器不判断机号(主、从方式)按传来的工作参数执行: 1、起始码(1 byte) (05H) 2、下位机固定地址(4bytes) (30H 30H 30H 30H) 3、遥控编码(8 bytes) (ASC码) 4、校验码 (2 bytes) (ASC码) 5、结束码(1 byte) (0DH) 二.)当空调控制器接收到如下数据时,表明空调控制器判断机号,且按传来的工作参数执行: 1、起始码(1 byte) (07H) 2、下位机地址(4bytes) (ASC码) (如地址=1023,ASC码=31H 30H 32H 33H) 3、遥控编码(8 bytes) (ASC码) 4、校验码 (2 bytes) (ASC码) 5、结束码(1 byte) (0DH) 三.)当空调控制器接收到如下数据时,表明设定、清除空调控制器机号,且按传来的工作参数执行: 1、起始码(1 byte) (0AH) 2、设定、清除下位机地址(4bytes) (ASC码) (如设置机号=1023,ASC码=31H 30H 32H 33H) (如清除机号=0000,ASC码=30H 30H 30H 30H) 3、遥控编码(8 bytes) (ASC码) 4、校验码 (2 bytes) (ASC码) 5、结束码(1 byte) (0DH) 四、空调控制器返回工作参数(24 bytes): 1、起始码(1 byte) (08H)1 2、本地机地址 (4 bytes) (ASC码)5 3、遥控编码(8 bytes) (ASC码)(扫风、换气和灯光要看状态1中的显示,这里

智能空调遥控器通信协议

智能空调遥控器 通信协议 ?概述 U-7071/7072 智能空调遥控通信协议采用标准MODBUS-RTU 协议,本协议规定了应用系统中主机与 U-7071/7072 之间在应用层的通信协议。U-7071可遥控 1 台空调,U-7072可控制2 台空调。 ?通信接口特性 接口类型:异步串行 RS485 通讯口。 通信波特率为:2400、4800、9600bps 可选,出厂默认为 9600bps。 数据传输格式:N, 8,1 说明:上位机与 U-7071/7072通信时间间隔不小于 50ms。 ?MODBU RTU 通信协议详述 ?命令格式 返回的每一个参数用两个字节有符号整型表示,高位在前,低位在后。 带符号整数范围 -32768~32767,上传数据需除以十,负数用补码表示。 如温度上传 16 进制 0xFF9C,高位为 1,表示负数,表示-10.0℃。 如温度上传 16 进制 0x00FA,对应十进制 250,表示 25.0℃。 进制 0x0258,对应十进制 600,表示 60.0%。 如湿度上传 16

说明: 通过RS485 接口发送空调遥控前,必须先按照说明书对原空调遥控器进行自学习,把需要通过RS485 进行远程控制的遥控命令自学习到U-7071/7072的储存器中。 ?调试案例 ?读温湿度数据 ?地址为 1,读温湿度数据 ?主机下发命令: 01 04 0000 0002 71CB (读温湿度) ?返回: 01 04 04,温度 H,温度 L,湿度 H,湿度 L,CRCL,CRCH。 ?空调遥控功能 ?地址为 1,发送遥控通道号 0 命令 ?主机下发命令: 01 05 0000 FF00 8C3A ??返回: 01 05 0000 FF00 8C3A ?来电自启动使能 ?地址为 1

艾默生-PEX空调技术参数说明

投标货物型号及主要技术参数说明 一、前言 针对机房空调市场不断发展的现状,为了提高我司机房空调在市场上的竞 争能力,满足客户日益严格的性能要求,公司推出了 Liebert.PEX 系列机房空 调产品,该系列产品在高可靠性、灵活性、生命周期内节能等方面具有明显的 市场竞争优势。Liebert.PEX 系列产品是基于艾默生全球研发与设计平台的高 端机组,针对全球销售,全球同步上市。 二、 整机系统说明 Liebert.PEX 系列空调产品在送风方式上分为上出风和下出风两类产品, 在系统配置上分为风冷型、水冷型、乙二醇冷却、冷冻水型。 上送风机组外观 下送风机组外观 1、 容量说明 Liebert.PEX 系列机组增加了大容量机组,最大容量机组 P3100 制冷量达到 了 100kW (8.6 万大卡), 。 2、 制冷系统配置说明 为了加强 Liebert.PEX 机组在市场上的竞争能力,除了在大容量机组上采用双 压缩机制冷系统外,也推出了大容量单压缩机制冷系统的机组,单压缩机系统最 大制冷量达到了 53kW ,具有很强的市场竞争力。在产品性能方面 Liebert.PEX 机 组的单压缩机大容量系统 P2045 和 P2055 采用双风机双电机系统结构,使送风系 统的功能更强大,调节范围更宽。当机房有多台机组 同时使用时,单系统机组可以作为一个模块来应用,不会影响整个机房的整体性能。 关于压缩机、风机数量,以及结构、冷量、主机尺寸的描述见下表。下表中的冷量数据为风冷、水冷机组下送风机型的数据,除冷量数据外,其它数据与上

送风机型相同。 Liebert.PEX 系统描述简表 3、风机系统 机组送风机外余压可以根据用户要求进行非标调整,对于风帽送风机外余压标准为25Pa,地板下送风标准为75Pa,对于风道送风产品标准送风压力为100Pa,风压调整范围为25~200Pa。超过200Pa 的风压要求请提前向公司申请。 4、电加热器加热量标准为一级,在需要增加加热量时可以增加第二级加热器。

空调型号命名规则

空调型号命名规则 (1)K—房间空调器。 (2)结构形式:F—分体式房间空调器;C—窗式房间空调器; (3)功能代号(单冷型无此代号):R—热泵型;D—电热型;RD—热泵辅助电热型。 (4)名义制冷量:用阿拉伯数字表示,其值取制冷量的前两位数。20、22、23代表一匹、25、26、28代表1.25匹、30、31、33、35、36代表1.5匹、40、45、50、60代表2匹、70代表3匹、120代表5匹 (5)分体式室内机组结构代号:L-柜式;G-壁挂式;C-窗式;N-内藏式;F-风管式;Q-嵌入式;D-吊顶式;W-室外机 (6)特殊功能:Y-遥控(仅限窗机);D-直流;BP-变频(美的: BP、格力:Fd);J-离子除尘;X-双向换风;F-负离子 如:KC-50/Y代表窗机,单冷,制冷量为5000W,为遥控型; KFR-35GW/BP表示壁挂分体式变频空调器,冷暖,制冷量为3500W。 空调适用面积参考

1P:11-17㎡ 1.25P:18-23㎡ 1.5P:18-25㎡2P:30-33㎡3P:40-45㎡5P:60㎡左右10P:100㎡左右 特推荐:空调器的命名有一套国家统一的标准,产品型号及含义如下: * * * * * * * * 1 2 3 4 5 6 7 8 1—表示产品代号(家用房间空调器用字母K表示) 2—表示气候类型(一般为T1型,T1型气候环境最高温度为43 C,T1型代号省略) 3—结构形式代号(空调器按结构形式分为整体式和分体式,整体式空调器又分为窗式和移动式,代号分别为:分体式—F、窗式—C、移动式—Y) 4—功能代号(空调器按功能主要分为单冷型、热泵型及电热型,单冷型代号省略,热泵型、电热型代号分别R、D) 5—规格代号(额定制冷量,用阿拉伯数字表示,空调器制冷量在10000W以下的,其单位为100W;制冷量大于或等于10000W时,其单位为1000W) 6—整体式结构分类代码或分体式室内机组结构分类代号(室内机组结构分类为吊顶式、挂壁式、落地式、天井式、嵌入式等,其代号分别为D、G、L、T、Q等) 7—室外机组结构代号(室外机组代号为W) 8—工厂设计序号和特殊功能代号等,允许用汉语拼音大写字母或阿拉伯数字表示。 下面以格力空调几个型号作简单说明 KCD-46(4620)其中K表示房间空调器,C表示窗机,D表示电热型,46表示制冷量是4600瓦。 KFR-25GW/E(2551)其中K表示房间空调器,F表示分体式,R表示热泵型,25表示制冷量是2500瓦,G表示挂壁式,W表示室外机代号,E表示冷静王系列产品。 KFR-50LW/E(5052LA)其中K表示房间空调器,F表示分体式,R表示热泵型,50表示制冷量是5000W,L表示落地式,W表示室外机代号。